An experimental study of the enhancement of air-cooling limits for telecom/datacom heat sink applications using an impinging air jet (Reprinted from IEEE ITHERM 2004 Proceedings - The Ninth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, June 1-4, 2004, Las Vegas, NV, USA)

被引:14
|
作者
Sansoucy, Eric [1 ]
Oosthuizen, Patrick H.
Refai-Ahmed, Gamal
机构
[1] Univ Ottawa, Dept Mech Engn, Ottawa, ON K1N 6N5, Canada
[2] Queens Univ, Dept Mech Engn, Kingston, ON K7L 3N6, Canada
[3] ATI Technol Inc, Markham, ON L3T 7X6, Canada
关键词
D O I
10.1115/1.2164848
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An experimental study was conducted to investigate the heat transfer from a parallel flat plate heat sink under a turbulent impinging air jet. A horizontal nozzle plate confined the target surface. The jet was discharged from a sharp-edged nozzle in the nozzle plate. Average Nusselt numbers are reported for Pr=0.7, 5000 <= Re <= 30,000, L/d=2.5, and 0.833 at H/d=3 where L, H, and d define the length of the square heat source, nozzle-to-target spacing, and nozzle diameter respectively. Tests were also conducted for an impinging flow over a flat plate, flush with the top surface of the target plate. The average Nusselt numbers from the heat sink were compared to those for a flat plate to determine the overall performance of the heat sink in a confined impingement arrangement. The experimental results were compared with the numerical predictions obtained in an earlier study. Although the average Nusselt numbers obtained from numerical simulations differed from the experimental measurements by 18%, the disagreement is much less significant when related to the junction temperature. Under typical conditions, it was shown that such discrepancy in the Nusselt number lead to an error of 6% in the prediction of the junction temperature of the device.
引用
收藏
页码:166 / 171
页数:6
相关论文
共 5 条