Two-Dimension Fault Line Selection Method Based on Transient Signal Features of Fault Phase

被引:0
|
作者
Zhang, Wenhai [1 ]
Yang, Jianwen [1 ]
Xiao, Xianyong [1 ]
Wang, Ying [1 ]
机构
[1] Sichuan Univ, Coll Elect Engn & Informat Technol, Chengdu 610065, Peoples R China
来源
PROGRESS IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2 | 2012年 / 354-355卷
关键词
Neutral non-effectively earthed system; Distribution system; Fault line selection; Gravity frequency; Transient signal energy; Two-dimension fault line selection criteria;
D O I
10.4028/www.scientific.net/AMR.354-355.1289
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
When single-line-to-ground fault happen in neutral non-effectively earthed system, there is a big difference between the fault feeder and un-fault feeder in transient signal energy centralized frequency band and signal amplitude of fault phase. The transient signal energy in fault feeder's fault phase is bigger, and it centralizes in lower frequency band. But the transient signal in un-fault feeders' has the contrary features. And this feature is affected little by the fault initial angle. So the paper proposed a method that using the gravity frequency and transient signal energy to form a two-dimension line selection method that using the signal overall distribution characteristics. It can be applied in neutral unearthed and resonant system simultaneously. And the method is effectively to different fault initial angle and fault resistance. The method is proved correctly, effectively and adaptively by actual simulation in different fault cases.
引用
收藏
页码:1289 / 1292
页数:4
相关论文
共 50 条
  • [1] New method of line selection for single phase grouding fault based on aggrandized transient current signal
    Schneider Electric Investment Co. Ltd., Beijing 100016, China
    不详
    Dianli Xitong Baohu yu Kongzhi, 2009, 19 (10-13): : 10 - 13
  • [2] Signal Model-Based Fault Detection and Diagnosis for Induction Motors Using Features of Vibration Signal in Two-Dimension Domain
    Do, Van Tuan
    Chong, Ui-Pil
    STROJNISKI VESTNIK-JOURNAL OF MECHANICAL ENGINEERING, 2011, 57 (09): : 655 - 666
  • [3] Single-Phase Fault Line Selection in Distribution Network Based on Signal Injection Method
    Niu, Lin
    Wu, Guiqing
    Xu, Zhangsheng
    IEEE ACCESS, 2021, 9 : 21567 - 21578
  • [4] Novel method of fault line selection by transient component for single-phase to ground fault in distribution networks
    College of Information and Control Engineering, China University of Petroleum, Dongying 257061, China
    Zhongguo Shiyou Daxue Xuebao (Ziran Kexue Ban), 2006, 3 (135-139+143):
  • [5] A Fault Feeder Selection Method Based On Transient Amplitude Fault Measure
    Yan, Guangtai
    Liang, Jiawen
    Wang, Xintao
    Liu, Anhua
    Bai, Yang
    PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY AND MANAGEMENT SCIENCE (ITMS 2015), 2015, 34 : 1127 - 1129
  • [6] A fault diagnosis method of the two-dimension image fractal theory based on time-frequency image
    Lin Tian
    Hao Zhi-Hua
    Li Bing
    ISTM/2007: 7TH INTERNATIONAL SYMPOSIUM ON TEST AND MEASUREMENT, VOLS 1-7, CONFERENCE PROCEEDINGS, 2007, : 3918 - 3921
  • [7] New method for single-phase-to-ground fault feeder selection based on analysis of fault transient characteristics
    Key Laboratory of Power System Simulation and Control of Ministry of Education, Tianjin University, Tianjin 300072, China
    不详
    Dianli Xitong Zidonghue, 2009, 16 (76-80):
  • [8] Study on T-Connection Transmission Line Fault Location Method Based on Transient Fault Traveling Wave Signal
    Zhang Zihao
    Yao Xiaodong
    2020 4TH INTERNATIONAL CONFERENCE ON MACHINE VISION AND INFORMATION TECHNOLOGY (CMVIT 2020), 2020, 1518
  • [9] New method for transient line selection in distribution system based on grounding fault transferred
    Li, Yilin
    Yin, Xianggen
    Chen, Rui
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2822 - 2826
  • [10] Single-pole fault line selection method of DC distribution network based on transient current fault component
    Gao S.
    Duan B.
    Song G.
    Shao M.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2022, 43 (03): : 141 - 146