Synchronous Condenser for European Grid Code Compliance: A Case Study of a PV Power Plant in Spain

被引:5
|
作者
Jimenez, Ruben Pascual [1 ]
Platero, Carlos A. A. [1 ]
Sanchez, Marcos Esteban [2 ]
Barneto, Eduardo Rivero [2 ]
机构
[1] Univ Politecn Madrid, Escuela Tecn Super Ingn Ind, Madrid 28006, Spain
[2] ESELEC, Madrid 28008, Spain
来源
IEEE ACCESS | 2023年 / 11卷
关键词
Reactive power; Codes; Renewable energy sources; Europe; Power system stability; Voltage control; Generators; Power grids; European grid code; inverter; reactive power capability; RMS simulations; renewable energy; robustness; synchronous condenser; OPTIMAL ALLOCATION; WIND;
D O I
10.1109/ACCESS.2023.3281532
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The massive integration of renewable energies into the grid towards the de-carbonisation of the power system has a major impact on the stability of the grid. This has led the European Union to establish guidelines on how renewable plants should be connected to the grid, in order to continue to guarantee their operation and stability. These requirements are contained in the European Grid Code. In this code, there are requirements concerning voltage control, reactive power capacity, fault-ride-through and short-circuit current contribution capabilities of renewable power plants. These plants, in particular those powered by photovoltaic inverters, have issues of reactive power capacity, so in order to be able to connect to the grid, they usually require an oversized of the inverters or the installation of reactive power compensation elements, such as capacitor banks, static VAR compensator or synchronous condensers. Moreover, the fault-ride-through and short-circuit current contribution are difficult to fulfil as they are inverter-based generators have a low capacity to supply short-circuit current and, in some cases, they disconnect from the grid. These facts have produced large power losses and protection malfunctions in power system with high photovoltaic power penetration. This paper studies the compliance of the European Grid Code of a 500 MW photovoltaic power plant with and without a synchronous condenser. The results show that not only the use of the synchronous condenser helps for reactive power regulation but also for fault-ride-through and short-circuit current contribution.
引用
收藏
页码:54713 / 54723
页数:11
相关论文
共 50 条
  • [1] Reliability indices improvement according to grid code compliance applied to PV power plants (Algerian grid code case study)
    Bahriya, Badache
    Hocine, Labar
    Samira, Kelaiaia Mounia
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2024,
  • [2] Proposal for an aggregated solar PV power plant simulation model for grid code compliance
    Martinez-Lavin, Miguel
    Villena-Ruiz, Raquel
    Honrubia-Escribano, Andres
    Hernandez, Jesus C.
    Gomez-Lazaro, Emilio
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 213
  • [3] Active and Reactive Power Control of a PV Generator for Grid Code Compliance
    Cabrera-Tobar, Ana
    Bullich-Massague, Eduard
    Aragues-Penalba, Monica
    Gomis-Bellmunt, Oriol
    ENERGIES, 2019, 12 (20)
  • [4] Permanent Magnet Synchronous Condenser for Wind Power Plant Grid Connection Support
    Hsu, Ping
    Muljadi, Eduard
    2015 9TH INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND ECCE ASIA (ICPE-ECCE ASIA), 2015, : 362 - 366
  • [5] Reputation of the Synchronous Condenser Technology in Modern Power Grid
    Igbinovia, Famous O.
    Fandi, Ghaeth
    Muller, Zdenek
    Tlusty, Josef
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2108 - 2115
  • [6] Case Study of Grid Connected Pv Plant Feeding Power to Electrical Submersible Pumps
    Sridhar, Yadavalli Venkata
    2016 IEEE INTERNATIONAL CONFERENCE ON POWER AND RENEWABLE ENERGY (ICPRE), 2016, : 547 - 552
  • [7] Superconductor synchronous condenser for reactive power support in an electric grid
    Kalsi, SS
    Madura, D
    Ingram, M
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2005, 15 (02) : 2146 - 2149
  • [8] Evaluation of the latest Spanish grid code requirements from a PV power plant perspective
    Martinez-Lavin, Miguel
    Villena-Ruiz, Raquel
    Honrubia-Escribano, Andres
    Hernandez, Jesus C.
    Gomez-Lazaro, Emilio
    ENERGY REPORTS, 2022, 8 : 8589 - 8604
  • [9] Equivalent Model of a Synchronous PV Power Plant
    Remon, Daniel
    Cantarellas, Antoni M.
    Abbas Elsaharty, Mohamed Atef
    Koch-Ciobotaru, Cosmin
    Rodriguez, Pedro
    2015 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2015, : 47 - 53
  • [10] Grid Code Compliance for Grid-Connecting a PV System to an Existing Facility in Singapore
    Brenda, L. G. H.
    Logenthiran, T.
    Yathunanthan, K.
    Amirthan, P.
    PROCEEDINGS OF THE 2016 IEEE REGION 10 CONFERENCE (TENCON), 2016, : 530 - 533