A hybrid control method for district heating substations based on time-based room temperature demand

被引:3
|
作者
Li, Zhiwei [1 ,2 ]
Liu, Junjie [1 ]
Zhang, Jian [2 ]
Wang, Yanmin [1 ,4 ]
Jia, Lizhi [3 ]
机构
[1] Tianjin Univ, Sch Environm Sci & Engn, Tianjin Key Lab Indoor Air Environm Qual Control, Tianjin 300072, Peoples R China
[2] Lanzhou Jiaotong Univ, Sch Environm & Municipal Engn, 88 Anning West Rd, Lanzhou 730070, Peoples R China
[3] Tianjin Univ Commerce, Tianjin Key Lab Refrigerat Technol, Tianjin 300134, Peoples R China
[4] Dalian Haixin Informat Engn Co Ltd, Dalian 116023, Liaoning, Peoples R China
关键词
District heating substation; Hybrid control; Hydraulic balance; Energy saving; SYSTEMS; IDENTIFICATION; SIMULATION;
D O I
10.1016/j.enbuild.2023.113467
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In China, the district heating (DH) substation serves as a large heating area and has different functions in buildings. However, the control methods of DH substations are yet to adjust the water supply temperature according to the existing outdoor meteorological parameters. Due to hydraulic imbalance, it is difficult to implement flexible control according to building functions, resulting in uneven heating in different buildings and high energy use. This study aims to implement demand heating through a hybrid control method (HCM) based on the dynamic demand of room temperatures. The HCM integrates centralized and distributed controls. First, the resistance identification and hydraulic balance calculations of the pipe network were performed according to the flow and pressure balance equation to maintain conditions close to the real working condition. Second, according to the most unfavorable loop room temperature, the secondary water supply temperature was corrected to ensure that the heat supply of the substation met the requirements. Finally, the distributed valve opening was corrected by room temperature feedback from each building to achieve accurate control of room temperature. This study considered a DH substation serving both residential and office buildings as an example. The dynamic simulation model was built for analysis. Compared with the conventional control method (CCM), the HCM can effectively overcome the uneven heating phenomenon, the fluctuation of room temperature was significantly reduced, and the thermal comfort was enhanced. The heating energy use of the DH substation was reduced by 12%. The energy use of office buildings was reduced by 27.5%-38.3%. The energy consumed by circulation pump operation was reduced by 16%. The cost-saving was approximately 2.57 RMB/m2, and the total cost-saving was 4.12 x 105 RMB. In this study, the problem of dynamic thermal balance of DH substations was solved with the proposed system, which effectively responds to the demand for heating while improving energy efficiency through a flexible control system.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Experimental evaluation of radiator control based on primary supply temperature for district heating substations
    Gustafsson, Jonas
    Delsing, Jerker
    van Deventer, Jan
    APPLIED ENERGY, 2011, 88 (12) : 4945 - 4951
  • [2] A dynamic control strategy of district heating substations based on online prediction and indoor temperature feedback
    Sun, Chunhua
    Chen, Jiali
    Cao, Shanshan
    Gao, Xiaoyu
    Xia, Guoqiang
    Qi, Chengying
    Wu, Xiangdong
    ENERGY, 2021, 235 (235)
  • [3] An energy performance assessment method for district heating substations based on energy disaggregation
    Lin, Xinyi
    Tian, Zhe
    Lu, Yakai
    Niu, Jide
    Cao, Yaqi
    ENERGY AND BUILDINGS, 2022, 255
  • [4] An energy performance assessment method for district heating substations based on energy disaggregation
    Lin, Xinyi
    Tian, Zhe
    Lu, Yakai
    Niu, Jide
    Cao, Yaqi
    Energy and Buildings, 2022, 255
  • [5] Dual room temperature target controlof district heating substation based on room temperature detection
    Li, Zhiwei
    Liu, Junjie
    Jia, Lizhi
    Wang, Yanmin
    Zhang, Jian
    Li, Yan
    Cheng, Hongjuan
    ENERGY AND BUILDINGS, 2024, 318
  • [6] Study of an Integrated Control Method for Heating Substations Based on Prediction of Water-Supply Temperature and Indoor Temperature
    Gao, Xiaoyu
    Jia, Meng
    Cao, Shanshan
    Qi, Chengying
    BUILDINGS, 2022, 12 (03)
  • [7] A method for setting room temperature of district heating in northern China based on local thermal comfort
    Liu, Chang
    Wang, Zhaojun
    Yang, Yuxin
    Zhou, Fanzhuo
    Duanmu, Lin
    Zhai, Yongchao
    Lian, Zhiwei
    Cao, Bin
    Zhang, Yufeng
    Zhou, Xiang
    Xie, Jingchao
    APPLIED THERMAL ENGINEERING, 2024, 253
  • [8] Novel effective room temperature-based predictive feedback control method for large-scale district heating substation
    Li, Zhiwei
    Liu, Junjie
    Yang, Xiaochen
    Huang, Xiuqi
    Jia, Lizhi
    Li, Min
    APPLIED THERMAL ENGINEERING, 2023, 218
  • [9] Fifth-Generation District Heating and Cooling Substations: Demand Response with Artificial Neural Network-Based Model Predictive Control
    Buffa, Simone
    Soppelsa, Anton
    Pipiciello, Mauro
    Henze, Gregor
    Fedrizzi, Roberto
    ENERGIES, 2020, 13 (17)
  • [10] Identification and evaluation of operation regulation strategies in district heating substations based on an unsupervised data mining method
    Lu, Yakai
    Tian, Zhe
    Peng, Peng
    Niu, Jide
    Dai, Jiping
    ENERGY AND BUILDINGS, 2019, 202