Experimental research on vapor-injected water source heat pump using R1234ze(E)

被引:8
|
作者
Wei, Falin [1 ]
Wang, Baolong [1 ]
Cheng, Zuo [2 ]
Cui, Mengdi [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing Key Lab Indoor Air Qual Evaluat & Control, Beijing 100084, Peoples R China
[2] Beijing Inst Mech Equipment, Beijing 100854, Peoples R China
关键词
Economizer systems; Alternative refrigerants; WSHP; ENERGY PERFORMANCE EVALUATION; TRIFLUOROACETIC-ACID; R1234YF; R134A; ALTERNATIVES; COMPRESSOR; SYSTEM; R450A;
D O I
10.1016/j.applthermaleng.2023.120595
中图分类号
O414.1 [热力学];
学科分类号
摘要
As a low GWP alternative refrigerant to R134a, the direct use of R1234ze(E) in water source heat pumps leads to significant performance degradation. Vapor injection combined with R1234ze(E) is a possible solution to this problem. In this study, a vapor-injected water source heat pump using R1234ze(E) as the working fluid was experimentally investigated. The results indicate that vapor injection using a flash tank or internal heat exchanger can significantly increase the coefficient of performance and heating capacity of the proposed heat pump. The improvements in the heating capacity and coefficient of performance corresponded to 22.3% and 8.1% for the flash tank system, and 19.5% and 7.3% for the internal heat exchanger system compared with the no-injection system.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] PERFORMANCE ANALYSIS FOR R1234ZE(E) USING IN VAPOR INJECTED HIGH TEMPERATURE HEAT PUMP WITH FLASH TANK.
    Zhao Panpan
    Jia Lei
    Zhou Junhai
    Qu Boyi
    Ke Yao
    Wang Rujin
    3RD IIR CONFERENCE ON HFO REFRIGERANTS AND LOW GWP BLENDS, 2023, : 198 - 205
  • [2] Experimental Testing of a Water-to-Water Heat Pump with and without IHX by Using Refrigerants R1234yf and R1234ze(E)
    Bosnjakovic, Mladen
    Santa, Robert
    Katinic, Marko
    SUSTAINABILITY, 2023, 15 (11)
  • [3] Experimental research on vapor-injected heat pump using injection subcooling
    Xu Shuxue
    Niu Jianhui
    Cui Zengyan
    Ma Guoyuan
    APPLIED THERMAL ENGINEERING, 2018, 136 : 674 - 681
  • [4] Experimental Investigation on High-temperature Heat Pump Water Heater of R1234ze
    Wu Zhijiang
    Liu Jinping
    Zhang Xuewei
    PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON ADVANCED DESIGN AND MANUFACTURING ENGINEERING, 2015, 39 : 1403 - 1406
  • [5] Numerical research on R32/R1234ze(E) air source heat pump under variable mass concentration
    Cheng, Zuo
    Wang, Baolong
    Shi, Wenxing
    Li, Xianting
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 82 : 1 - 10
  • [6] Low GWP refrigerants R1234ze(E) and R1234ze(Z) for high temperature heat pumps
    Fukuda, Sho
    Kondou, Chieko
    Takata, Nobuo
    Koyama, Shigeru
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2014, 40 : 161 - 173
  • [7] R1234yf and R1234ze(E) as low-GWP refrigerants for residential heat pump water heaters
    Nawaz, Kashif
    Shen, Bo
    Elatar, Ahmed
    Baxter, Van
    Abdelaziz, Omar
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 82 : 348 - 365
  • [8] Experimental analysis of the use of R1234yf and R1234ze(E) as drop-in alternatives of R134a in a water-to-water heat pump
    Maria Colombo, Luigi Pietro
    Lucchini, Andrea
    Molinaroli, Luca
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 115 : 18 - 27
  • [9] A Novel Ground-Source Heat Pump with R744 and R1234ze as Refrigerants
    Emmi, Giuseppe
    Bordignon, Sara
    Carnieletto, Laura
    De Carli, Michele
    Poletto, Fabio
    Tarabotti, Andrea
    Poletto, Davide
    Galgaro, Antonio
    Mezzasalma, Giulia
    Bernardi, Adriana
    ENERGIES, 2020, 13 (21)
  • [10] First experimental results of the use of R1234yf and R1234ze(E) as drop-in substitutes for R134a in a water-to-water heat pump
    Molinaroli, L.
    Lucchini, A.
    Colombo, L. P. M.
    Bocchinfuso, F.
    37TH UIT HEAT TRANSFER CONFERENCE, 2020, 1599