Nozzle arrangement study for pre-cooling the inlet air of natural draft dry cooling tower under crosswinds

被引:8
|
作者
Pang, Huimin [1 ]
Wang, Mingwei [2 ]
Gao, Qi [1 ,2 ]
Cheng, Shen [3 ]
Liu, Zhilan [4 ]
Geng, Zhe [5 ]
Zhang, Shuzhen [5 ]
He, Suoying [1 ]
Liu, Tiantian [1 ]
Zhao, Cuilin [1 ]
Liu, Wangrui [1 ]
Gao, Ming [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Shandong Engn Lab High Efficiency Energy Conservat, Jinan 250061, Shandong, Peoples R China
[2] Shandong Casen Heat Transfer Technol Co Ltd, Weifang 261055, Shandong, Peoples R China
[3] Qilu Univ Technol, Sch Energy & Power Engn, Jinan 250353, Shandong, Peoples R China
[4] Himile Mech Sci & Technol Shandong Co Ltd, Weifang 261550, Shandong, Peoples R China
[5] Shandong Hetong Informat Technol CO LTD, Jinan 250013, Shandong, Peoples R China
关键词
Natural draft dry cooling tower; Nozzle spray; Arrangement; Crosswind; Numerical simulation; WATER SPRAY; NUMERICAL-SIMULATION; THERMAL PERFORMANCE; WETTED MEDIA; WIND; SYSTEM; ENHANCEMENT; SHRINKAGE; DESIGN; FLOW;
D O I
10.1016/j.ijrefrig.2023.01.011
中图分类号
O414.1 [热力学];
学科分类号
摘要
Crosswind affects the airflow fields of the natural draft dry cooling towers (NDDCTs), thus the spray zones for pre-cooling the inlet air of the NDDCT might be different from no crosswind. Therefore, a 3-D model of pre-cooled NDDCT under crosswind was established by Fluent 16.2 to investigate the feasible zone of nozzle spray of a 120 m high NDDCT based on the behavior of the droplets. Six nozzle heights, nine nozzle radiuses and four spray angles were simulated for the NDDCT application within the crosswind speeds of 0 similar to 10 m/s. The evaporation percentage of droplets higher than 99% and the maximum effective evaporation ratio are selected as the criterion for the feasible zone of nozzle arrangement. Simulation finds that: (1) the nozzle arrangement height should be set at 7 m when the crosswind speed is 0 m/s, and it should be set at 9 m when the crosswind speeds are 2 m/s, 4 m/s,6 m/s, 8 m/s and 10 m/s, respectively. (2) The feasible spray angles of nozzles are 0 degrees and 90 degrees at the crosswind speeds of 0 similar to 4 m/s and 6 similar to 10 m/s, respectively. (3) The nozzle radiuses are 0 similar to 41.5 m at crosswind speed of 0 m/s, they are 0 similar to 21.5 m at the crosswind speed of 2 m/s, and they are 0 similar to 16.5 m when the crosswind speeds are 4 m/s, 6 m/s, 8 m/s and 10 m/s, respectively based on the above feasible heights and spray angles. The results will provide a guidance for nozzle design of spray pre-cooled NDDCT under crosswinds.
引用
收藏
页码:1 / 12
页数:12
相关论文
共 50 条
  • [1] Investigation on feasible zone of nozzle spray for pre-cooling the inlet air of natural draft dry cooling tower
    Pang, Huimin
    Zhao, Chunrong
    Cheng, Shen
    Wang, Mingwei
    Gao, Qi
    He, Suoying
    Sun, Gengsheng
    Jiang, Guangxu
    Sun, Qinggang
    Liu, Zhilan
    Geng, Zhe
    Zhang, Shuzhen
    Gao, Ming
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 38
  • [2] Investigations on the influence of nozzle arrangement on the pre-cooling effect for the natural draft dry cooling tower
    Sun, Yubiao
    Guan, Zhiqiang
    Gurgenci, Hal
    Hooman, Kamel
    Li, Xiaoxiao
    APPLIED THERMAL ENGINEERING, 2018, 130 : 979 - 996
  • [3] Investigation on the control mechanism of spray pre-cooling the inlet air of natural draft dry cooling tower
    He, Suoying
    Li, Yang
    Wang, Mingwei
    Wang, Aiping
    Alkhedhair, Abdullah M.
    Guan, Hongjun
    Wu, Xuehong
    Shi, Yuetao
    Gao, Ming
    APPLIED THERMAL ENGINEERING, 2022, 217
  • [4] Investigation on the spray strategy for the inlet air pre-cooling of natural draft dry cooling tower under typical crosswind
    Liu, Tiantian
    Wang, Jucheng
    Song, Tianyi
    He, Suoying
    Zhan, Jianwei
    Geng, Zhe
    Zhang, Shuzhen
    Huang, Xiang
    Qi, Jianhui
    Gao, Ming
    Shi, Yuetao
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2023, 239
  • [5] Water spray for pre-cooling of inlet air for Natural Draft Dry Cooling Towers - Experimental study
    Alkhedhair, Abdullah
    Guan, Zhiqiang
    Jahn, Ingo
    Gurgenci, Hal
    He, Suoying
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2015, 90 : 70 - 78
  • [6] THE INLET AIR PRE-COOLING OF NATURAL DRAFT DRY COOLING TOWERS-WETTED MEDIUM ISSUE
    He, Suoying
    Zhang, Guanhong
    Xu, Yi
    Sun, Fengzhong
    PROCEEDINGS OF THE ASME POWER CONFERENCE JOINT WITH ICOPE-17, 2017, VOL 1, 2017,
  • [7] Numerical simulation of water spray for pre-cooling of inlet air in natural draft dry cooling towers
    Alkhedhair, Abdullah
    Gurgenci, Hal
    Jahn, Ingo
    Guan, Zhiqiang
    He, Suoying
    APPLIED THERMAL ENGINEERING, 2013, 61 (02) : 416 - 424
  • [8] Experimental study of the application of two trickle media for inlet air pre-cooling of natural draft dry cooling towers
    He, Suoying
    Guan, Zhiqiang
    Gurgenci, Hal
    Hooman, Kamel
    Lu, Yuanshen
    Alkhedhair, Abdullah M.
    ENERGY CONVERSION AND MANAGEMENT, 2015, 89 : 644 - 654
  • [9] A study on multi-nozzle arrangement for spray cooling system in natural draft dry cooling tower
    Sun, Yubiao
    Guan, Zhioliang
    Gurgenci, Hal
    Li, Xiaoxiao
    Hooman, Kamel
    APPLIED THERMAL ENGINEERING, 2017, 124 : 795 - 814
  • [10] Parametric study on spray cooling system for optimising nozzle design with pre-cooling application in natural draft dry cooling towers
    Alkhedhair, Abdullah
    Jahn, Ingo
    Gurgenci, Hal
    Guan, Zhiqiang
    He, Suoying
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2016, 104 : 448 - 460