Evaluation of correlations for mass flow rate of refrigerant through electronic expansion valve in air-water heat pump system using R32

被引:5
|
作者
Kim, Min Kyu [1 ]
Lee, Hyoin [1 ]
Jeong, Ji Hwan [1 ]
机构
[1] Pusan Natl Univ, Sch Mech Engn, 2 Busandaehang Ro 63 Beon Gil, Busan 46241, South Korea
基金
新加坡国家研究基金会;
关键词
R32; Mass flow rate; Heat pump; Electronic expansion valve; Expansion device; OIL CIRCULATION RATE; EMPIRICAL CORRELATION; R22; PERFORMANCE; R410A; TUBE; SIMULATION; WORKING; R245FA;
D O I
10.1016/j.ijrefrig.2023.03.020
中图分类号
O414.1 [热力学];
学科分类号
摘要
To measure mass flow rate of R32 through EEVs under real operating conditions, a commercially available airwater heat pump (AWHP) system was operated in as wide a range as possible. Measurements showed that the effect of oil circulation on the refrigerant mass flow rate of the test system was negligible. To examine whether they were able to predict refrigerant mass flow rate of R32 in a real operating heat pump systems, previous empirical correlations available in the open literature were compared against these measured data. Previous empirical correlations, except for those of Park et al. (2007), showed poor agreement with the present experimental data, with mean absolute percentage error (MAPE) from 9.1% to 334.5% for EEV#1 (D: 2.40 mm) and from 24.1% to 122.2% for EEV#2 (D: 1.65 mm). These large differences were caused by differences in internal geometry of flow passage and operating conditions due to different refrigerants. A new empirical correlation was developed considering these aspects. The valve opening ratio was considered in terms of the valve flow coefficient variation. The thermodynamic state of refrigerant at the EEV inlet was represented by the enthalpy difference, so as to avoid discontinuity of the mathematical expression at the saturated liquid point. The new correlation showed good agreement with mass flow rate measured through both EEVs, with MAPE values of 9.3% and 14.5% for EEV#1 (D: 2.40 mm) and EEV#2 (D: 1.65 mm), respectively.
引用
收藏
页码:267 / 277
页数:11
相关论文
共 12 条
  • [1] Study on Economized Vapor Injection Heat Pump System Using Refrigerant R32
    Shi, Yaoguang
    Guo, Xianmin
    Zhang, Xinyu
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2016, 24 (01)
  • [2] Mass flow characteristics and correlations of R454C flow through an electrical expansion valve in a heat pump split system
    Hou, Weigang
    Liu, Haotian
    Braun, James E.
    Groll, Eckhard A.
    Ziviani, Davide
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 155 : 375 - 386
  • [3] PERFORMANCE EVALUATION OF A LARGE CAPACITY AIR-WATER HEAT PUMP USING PROPANE AS REFRIGERANT
    Xu, T.
    Sawalha, S.
    Mazzoti, W.
    Palm, B.
    12TH IIR GUSTAV LORENTZEN NATURAL WORKING FLUIDS CONFERENCE, 2016, : 559 - 566
  • [4] FLOW CHARACTERISTICS OF ELECTRONIC EXPANSION VALVES FOR HEAT PUMP SYSTEM USING CARBON DIOXIDE AS A REFRIGERANT
    Kim, Ook Joong
    Choi, Young-Ho
    Yoon, Seok Ho
    PROCEEDINGS OF THE ASME FLUIDS ENGINEERING DIVISION SUMMER CONFERENCE - 2010 - VOL 1, PTS A-C, 2010, : 1041 - 1046
  • [5] Experimental Study on Performance of Flash-tank Vapor Injection Air-Source Heat Pump System with Refrigerant R32
    Xue Jie
    Guo Xianmin
    Xue Liping
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 950 - 956
  • [6] Research on heat source transformation of radiator heating system using R32 air-cooled heat-pump unit
    Zhou, Yanrui
    Guan, Xiaoman
    ADVANCES IN ENERGY SCIENCE AND EQUIPMENT ENGINEERING, 2015, : 2479 - 2482
  • [7] A new empirical mass flow correlation and mass flow rate characteristics of R600a through novel rotary-baffle curved-channel electronic expansion valve
    Yang, Yikun
    Huang, Dong
    Zhao, Rijing
    Wei, Xinghua
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 168 : 70 - 78
  • [8] Mass flow rate prediction of direct-expansion solar-assisted heat pump using R290 based on ANN model
    Kong, Xiangqiang
    Ma, Shanle
    Ma, Tingdong
    Li, Ying
    Cong, Xiaochun
    SOLAR ENERGY, 2021, 215 : 375 - 387
  • [9] Energy and exergy analysis of an air-source heat pump water heater system using CO2/R170 mixture as an azeotropy refrigerant for sustainable development
    Wang, Dong
    Liu, Yaru
    Kou, Zunli
    Yao, Lifang
    Lu, Yuehong
    Tao, Leren
    Xia, Peng
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 106 : 628 - 638
  • [10] Evaluation of Seasonal Performance Improvements in a 3-Ton Air-Conditioning Heat Pump System Using a Novel Design of Integrated Electronic Expansion Valves and Distributors
    Bowers, Chad D.
    Wrocklage, Dave
    Elbel, Stefan
    Hrnjak, Predrag
    ASHRAE TRANSACTIONS 2014, VOL 120, PT 1, 2014, 120