Short- and long-term heating performances and optimization of solar heating coupled with groundwater source heat pump (SH-GWSHP) system for 24-h running buildings in Tibetan Plateau, China

被引:3
|
作者
Shi, Boqin [1 ]
Li, Yongcai [1 ]
Lu, Jun [1 ]
Kong, Xiangfei [2 ]
Wang, Qiwei [3 ]
Li, Yong [3 ]
机构
[1] Chongqing Univ, Sch Civil Engn, Chongqing 40045, Peoples R China
[2] Hebei Univ Technol, Sch Energy & Environm Engn, Tianjin 300401, Peoples R China
[3] Army Engn Univ PLA, Inst Mil Environm Teaching & Res, Nanjing 210007, Peoples R China
关键词
Solar energy; Groundwater source heat pump; Heating performance; Field measurement; Optimization; THERMAL PERFORMANCE; ENERGY UTILIZATION; POVERTY; CHIMNEY; AREAS;
D O I
10.1016/j.applthermaleng.2024.122609
中图分类号
O414.1 [热力学];
学科分类号
摘要
Tibet is rich in solar energy and has significant heating demand for buildings. Hence, developing a multi-source complementary heating system based on solar energy is a feasible approach to address local heating issues in the Tibetan area. However, the design of a solar energy-based heating system for 24-h running buildings is challenging due to the mismatch between solar energy availability and nocturnal heating load. To fill this gap, a solar heating system coupled with a groundwater source heat pump (SH-GWSHP) is proposed in this study. The heating performance of the proposed SH-GWSHP system for 24-h buildings under Tibetan weather conditions is explored and optimized. A field test is conducted to assess the short-term performance of the SH-GWSHP system at Xigaze Peace Airport. Furthermore, a transient system simulation (TRNSYS) model of the coupled heating system is developed and utilized to analyze and optimize long-term system performance. The results show that the average temperature of a water tank is higher than 50 degrees C for 4 h and the measured energy efficiency ratios (EERs) of the SH system, combination heating mode, and GWSHP system are 8.52, 3.79, and 3.38, respectively. The maximum daily average collector efficiency is 0.4 and the average value is approximately 0.3 during the middle heating period. In addition, the overall solar fraction is only 0.20 over the entire heating season. The optimal volume of the water tank for performance optimization is 30 m(3). The collector area should be maximized to fully utilize solar energy for heating, and the temperature of the heating water should be minimized to achieve optimal heating efficiency.
引用
收藏
页数:13
相关论文
共 2 条
  • [1] Economic optimization of auxiliary heat source for centralized solar district heating system in Tibetan Plateau, China
    Zhang, Ruichao
    Wang, Dengjia
    Liu, Yanfeng
    Chen, Yaowen
    Fan, Jianhua
    Song, Cong
    Wang, Yingying
    ENERGY CONVERSION AND MANAGEMENT, 2021, 243
  • [2] A novel heating strategy and its optimization of solar-air source heat pump heating system for rural buildings in northwest China
    Yan, Xiuying
    Xia, Yu
    He, Xuxin
    JOURNAL OF RENEWABLE AND SUSTAINABLE ENERGY, 2024, 16 (03)