Signal Processing for High Impedance Differential Protection Schemes

被引:0
|
作者
Tourn, Daniel Humberto [1 ]
Florena, Edgardo [1 ]
Zamanillo, German [1 ]
Donolo, Pablo Daniel [1 ]
Dissanayake, Anushka [2 ]
Kulkarni, Pallavi [2 ]
Hartshorn, Jay [2 ]
Donolo, Marcos [2 ]
机构
[1] UNRC, Fac Ingn, 5804BYA, Rio Cuarto, Argentina
[2] SEL Schweitzer Engn Labs Inc, Pullman, WA 99163 USA
关键词
Relays; Protection; Impedance; Resistors; Circuit faults; Fault currents; Signal processing; Bus bar protection; high impedance differential protection; phasor generation; signal processing;
D O I
10.1109/TIA.2024.3427051
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
High Impedance differential protections (87Z) schemes for bus and transformer Restricted Earth Fault (REF) applications are common in the industry because of their security, dependability, and simplicity. 87Z schemes consist of a dedicated set of CTs, one per terminal, with all the secondary windings connected in parallel and terminated at a resistor, referred to as a stabilizing resistor, and MOVs. The interaction of these components results in voltage and current signals that deviate from typical power systems signals. In this paper, we present data from testing at a 2 MVA test facility and draw conclusions from the effect of these distortions on the signal processing of protective relays. We show that these effects are limited to a narrow range of fault currents. We also present signal processing and logic for the 87Z scheme that is secure and dependable.
引用
收藏
页码:7702 / 7710
页数:9
相关论文
共 50 条
  • [1] High Impedance Differential protection system versus Low Impedance Differential protection system
    Jankovic, Ilija
    2015 68TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2015, : 898 - 942
  • [2] BUS DIFFERENTIAL PROTECTION - PRINCIPLES AND APPLICATION OF MODERATE IMPEDANCE SCHEMES.
    Rao, S.M.Subba
    Journal of the Institution of Engineers (India): Electrical Engineering Division, 1980, 61 (pt EL 3): : 101 - 106
  • [3] Comparison between high impedance and low impedance bus differential protection
    Holbach, Juergen
    2009 62ND ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2009, : 548 - 562
  • [4] Comparison between high impedance and low impedance bus differential protection
    Holbach, Juergen
    2009 POWER SYSTEMS CONFERENCE, 2009, : 164 - 179
  • [5] Misoperation of high impedance differential protection for main transformer
    Yuan, Cheng
    Tai, Nengling
    Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2008, 28 (08): : 121 - 123
  • [6] A Review of High-Impedance and Low-Impedance Differential Relaying for Bus Protection
    Pavavicham, Suparat
    Johnson, Gerald
    2014 67TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2014, : 723 - 737
  • [7] Redundant Bus Protection Using High-Impedance Differential Relays
    LaBlanc, Josh
    Thompson, Michael J.
    2018 71ST ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS (CPRE), 2018,
  • [8] High Frequency Impedance Differential Protection With High Proportion of Photovoltaic Power Distribution Network
    Chao C.
    Zheng X.
    Gao P.
    Tai N.
    Tu Q.
    Sun T.
    Li W.
    An Y.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (20): : 6968 - 6978
  • [9] UNIFIED APPROACH TO DIFFERENTIAL AND IMPEDANCE PROTECTION
    MALIK, OP
    HOPE, GS
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (01): : 16 - 16
  • [10] Analysis of Signal Processing Techniques for High Impedance Fault Detection in Distribution Systems
    Lopes, Gabriela Nunes
    Lacerda, Vinicius Albernaz
    Vieira, Jose Carlos Melo
    Coury, Denis Vinicius
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (06) : 3438 - 3447