CO2 Heat Pump in High-Temperature District Heating Plant

被引:0
|
作者
Eggen, G. [1 ]
Skinnes, K. [2 ]
Engen, M. [3 ]
Ingebrigtsen, M. [3 ]
Smedegard, O. O. [1 ]
机构
[1] COWI AS, Lyngby, Denmark
[2] Nour Consulting AS, Copenhagen, Denmark
[3] Svolvaer, Nordland Cty, Norway
关键词
Heat Pumps. District Heating; Ground-Source Heat Pump; Carbon Dioxide;
D O I
10.18462/iir.gl2022.0129
中图分类号
O414.1 [热力学];
学科分类号
摘要
In 2019, an oil-fired boiler was replaced by a ground-source CO2 heat pump system in a military facility in Norway. The facility was heated by a district heating plant with forward temperatures up to 80 degrees C, and return temperatures varying from 35 degrees C to 55 degrees C. These relatively high return temperatures result in low COP for the CO2 heat pump. Nevertheless, CO2 was chosen as refrigerant for the heat pump because the high forward temperature was a serious obstacle for the alternative HFO1234ze heat pump system. The CO2 heat pump system was competitive with regard to energy savings as well as profitability compared with the alternative HFO heat pump. The CO2 heat pump system has performed well, and the energy savings have been greater than expected. One of the reasons for that is due to the implemented measures in the district heating network in order to reduce the district heating water return temperatures.
引用
收藏
页码:510 / 515
页数:6
相关论文
共 50 条
  • [1] HIGH-TEMPERATURE HEAT PUMP INTEGRATION INTO DISTRICT HEATING SYSTEM
    Jakovleva, Ludmila
    20TH INTERNATIONAL SCIENTIFIC CONFERENCE ENGINEERING FOR RURAL DEVELOPMENT, 2021, : 1312 - 1316
  • [2] Analysis of the dilatancy technology of district heating system with high-temperature heat pump
    Wang Ying
    Zhang Yufeng
    ENERGY AND BUILDINGS, 2012, 47 : 230 - 236
  • [3] Transcritical-transcritical cascade CO2 heat pump cycles for high-temperature heating: A numerical evaluation
    Kong, Lana
    Walmsley, Timothy Gordon
    Hoang, Duy Khanh
    Schlosser, Florian
    Chen, Qun
    Carson, James K.
    Cleland, Donald John
    APPLIED THERMAL ENGINEERING, 2024, 238
  • [4] Characteristic analysis and performance optimization of a transcritical CO2 heat pump for high-temperature heating: An experimental study
    Yang, Lingxiao
    Wang, Xin
    Xu, Bo
    Chen, Zhenqian
    RENEWABLE ENERGY, 2024, 237
  • [5] Analysis and experiment of dilatancy technology of district heating system with high-temperature heat pump
    Wang, Ying
    Zhang, Yu-Feng
    Zhang, Y.-F. (yufengfa@tju.edu.cn), 2012, Tianjin University (45): : 981 - 986
  • [6] Modelling the performance of a transcritical CO2 heat pump for high temperature heating (Reprinted)
    White, SD
    Yarrall, MG
    Cleland, DJ
    Hedley, RA
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (04): : 479 - 486
  • [7] Design, construction, and commissioning of a 500 kW high-temperature heat pump plant for the district heating network of Bochum, Germany
    Passamonti, Arianna
    Sachse, Frank
    Bombarda, Paola
    Bracke, Rolf
    ENERGY REPORTS, 2025, 13 : 548 - 561
  • [8] High-temperature heat pumps for district heating supply
    Hochtemperaturwärmepumpen für die Fernwärmeversorgung
    Schmid, Wolfgang (wsm@tele2.de), 1600, Verlags und Wirtschaftsges. der Elektrizitatswerke (50): : 7 - 8
  • [9] High temperature heat pump integration into district heating network
    Mateu-Royo, Carlos
    Sawalha, Samer
    Mota-Babiloni, Adrian
    Navarro-Esbri, Joaquin
    ENERGY CONVERSION AND MANAGEMENT, 2020, 210 (210)
  • [10] Investigation of a High-Temperature Heat Pump for Heating Purposes
    Bellos, Evangelos
    Tsimpoukis, Dimitrios
    Lykas, Panagiotis
    Kitsopoulou, Angeliki
    Korres, Dimitrios N.
    Vrachopoulos, Michail Gr.
    Tzivanidis, Christos
    APPLIED SCIENCES-BASEL, 2023, 13 (04):