Algorithm for Automated Assessment of the Condition of a High-Voltage SF6 Circuit Breaker Based on a Limited Data Set

被引:0
|
作者
Sorokin, A.S. [1 ]
Kovalenko, A.I. [1 ]
Maliuten, M.S. [1 ]
Lebedev, A.A. [1 ]
Sultanov, M.M. [2 ]
Strizhichnko, A.V. [2 ]
机构
[1] National Research University Moscow Power Engineering Institute, Moscow, Russia
[2] Volzhsky Branch of National Research University Moscow Power Engineering Institute, Volzhsky, Russia
关键词
Circuit-breakers - Condition - Equipment maintenance - Equipment repair - Failure risk - Health indices - Limited data sets - Machine-learning - Risk-based approach - SF 6;
D O I
10.1007/s10749-024-01818-7
中图分类号
学科分类号
摘要
One of the main tasks of condition-monitored maintenance and repair of electrical equipment is to assess its technical condition. The current regulations provide a procedure for assessing the technical condition of electrical equipment by calculating the health index (HI). To calculate the HI of a 110 kV tank-type SF6 circuit breaker, it is necessary to evaluate 46 parameters. The value of the HI should be updated and predicted for the next 5 years at least once a year. However, to update about half of the 46 parameters, it is required to disable the circuit breaker. This paper proposes an algorithm for automating the evaluation of the HI of a circuit breaker and determining the HI from a limited set of data obtained from the automated systems installed at the facility. A complete set of retrospective data is used for machine learning model, which allows automatic calculation of the HI of the circuit breaker during operation without the participation of maintenance personnel. Retrospective data on 20% of like equipment are used for training the model. After that, the HI of the remaining equipment can be automatically determined from a limited data set, without human intervention. This will allow us to reduce the resources for calculating the HIs of circuit breakers and to determine the HI of a circuit breaker during operation, without taking it out of operation © Springer Science+Business Media, LLC, part of Springer Nature 2024.
引用
收藏
页码:344 / 348
页数:4
相关论文
共 50 条
  • [1] Dielectric recovery in a high-voltage circuit breaker in SF6
    Seeger, M.
    Schwinne, M.
    Bini, R.
    Mahdizadeh, N.
    Votteler, T.
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2012, 45 (39)
  • [2] An Online Non-Invasive Condition Assessment Method of Outdoor High-Voltage SF6 Circuit Breaker
    Da Silva, Clailton Leopoldo
    Reis, Osmar
    Assuncao, Frederico de Oliveira
    Castioni, Julio Cezar Oliveira
    Martins, Rafael
    Xavier, Carlos Eduardo
    Areias, Isac Antonio dos-Santos
    Lambert-Torres, Germano
    Bonaldi, Erik Leandro
    Borges-da-Silva, Luiz Eduardo
    Oliveira, Levy Ely Lacerda
    MACHINES, 2023, 11 (03)
  • [3] An overall condition monitoring system of high voltage SF6 circuit breaker
    Dong, Yue
    Xiao, Dengming
    WSEAS Transactions on Circuits and Systems, 2007, 6 (03): : 397 - 402
  • [4] Interruption Characteristics of High-voltage Hybrid Circuit Breaker Based on the Alternative of SF6 Gas
    Cheng X.
    Chen Z.
    Ge G.
    Jiao L.
    Liao M.
    Gaodianya Jishu, 12 (3862-3868): : 3862 - 3868
  • [5] A condition assessment algorithm based on Dynamic Time Warping for high-voltage circuit breaker
    Ermidoro, Michele
    Previdi, Fabio
    2016 12TH IEEE INTERNATIONAL CONFERENCE ON CONTROL AND AUTOMATION (ICCA), 2016, : 167 - 172
  • [6] SF6 High-Voltage Circuit Breaker Contact Status Detection at Different Currents
    Guo, Ze
    Li, Linjing
    Han, Weimeng
    Guo, Zixuan
    SENSORS, 2022, 22 (21)
  • [7] A Novel Intelligent High Voltage SF6 Circuit Breaker
    Liu, Jun
    Huang, Garng M.
    Ma, Zhiying
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,
  • [8] High Voltage SF6 Circuit Breaker Selection for a Substation
    Azam, A. B. M. Shafiul
    Schmidt, William Hal
    Elford, Kellie
    Vicklund, Kevin
    Dymond, Matt
    2022 IEEE PES GENERATION, TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION - LATIN AMERICA, IEEE PES GTD LATIN AMERICA, 2022,
  • [9] Optimization of extra-high-voltage SF6 circuit breaker based on improved genetic algorithm
    Liu, Xiaoming
    Cao, Yundong
    Wen, Fuyue
    Wang, Erzhi
    IEEE TRANSACTIONS ON MAGNETICS, 2008, 44 (06) : 1138 - 1141
  • [10] A real gas model for numerical flow analysis in a high-voltage SF6 circuit breaker
    Bosovic, B.
    Beslija, D.
    Kim, M. H.
    Torlak, M.
    Dzaferovic, E.
    Kapetanovic, M.
    PROCEEDINGS OF THE EIGHTH INTERNATIONAL SYMPOSIUM ON TURBULENCE HEAT AND MASS TRANSFER (THMT-15), 2015, : 767 - 770