Research on transient characteristics and test technology of electronic voltage transformer based on digital-physical hybrid simulation

被引:0
|
作者
Wang Y. [1 ]
Tang H. [2 ]
Gao B. [1 ]
Zheng G. [1 ]
Ding J. [1 ]
机构
[1] State Grid Anhui Electric Power Research Institute, Hefei
[2] Jiangsu Lingchuang Electric Automation Co., Ltd., Zhenjiang
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2019年 / 47卷 / 06期
关键词
Digital-physics hybrid simulation; Electronic voltage transformer; Fault component test; Resistive-capacitive divider; Transient error; Transient transmission characteristics;
D O I
10.7667/PSPC180454
中图分类号
学科分类号
摘要
According to the principle structure of the resistor-capacitor voltage-divided electronic voltage transformer, the transient transfer characteristics of the resistor-capacitor voltage-divided electronic transformer after differential integration are analyzed. With relay protection application, the influence of transient voltage transfer characteristics of electronic voltage transformer on fast distance protection is studied. A digital voltage transformer transient test technology scheme based on digital physics hybrid simulation is proposed. The small voltage signal is digitally simulated and amplified by a power amplifier. The physical simulation platform of the electronic voltage transformer resistance-capacitor voltage divider is built and a complete test system is established. The initial time is determined by the mutation detection, and the analog raw voltage signal and the digital signal of the sample are synchronously acquired, then, the transient error calculation of the electronic voltage transformer in the transient process is performed. The feasibility of the test technology solution is verified by the application of the developed test system in the laboratory. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:125 / 131
页数:6
相关论文
共 18 条
  • [1] Li X., Huang J., Ni C., Et al., Influence of mixing different types of current transformers on line differential protection and the countermeasures, Power System Protection and Control, 42, 3, pp. 141-145, (2014)
  • [2] Ni C., Zhang K., Yang S., Et al., Application of R-L model distance protection based on ECT, Power System Protection and Control, 40, 15, pp. 132-135, (2012)
  • [3] Li C., Li Q., Li Z., Et al., DC magnetic bias and remanence while under the effect of protection of transient characteristic of current transformer, Power System Protection and Control, 38, 23, pp. 107-111, (2010)
  • [4] Dai W., Zheng Y., Bai L., Et al., Analysis of protective current transformer transient response, Power System Protection and Control, 45, 19, pp. 46-54, (2017)
  • [5] Fan Z., Bai S., Yang Z., Et al., Research on key technology of optical current transformer, Power System Protection and Control, 46, 3, pp. 67-74, (2018)
  • [6] Kang X., Zhang X., Suonan J., Et al., Influence of transient characteristics of capacitor voltage transformer and current transformer on distance protection, Journal of Xi'an Jiaotong University, 40, 8, pp. 955-960, (2006)
  • [7] Zhang B., Hao Z., Bo Z., New development in relay protection for smart grid, Protection and Control of Modern Power Systems, 1, 1, pp. 121-127, (2016)
  • [8] Wang J., Guo Z., Zhang G., Et al., Investigation and simulation of transient characteristics of electronic voltage transformer, Electric Power Automation Equipment, 32, 3, pp. 62-65, (2012)
  • [9] Zhang K., Wang N., Duan X., Et al., Digital integrator for electronic current transformer, Proceedings of the CSEE, 24, 12, pp. 104-108, (2004)
  • [10] Liu Q., Xu Y., Gao F., Et al., Simulation research on electronic voltage transformer transient process, Journal of Electrical Engineering, 10, 10, pp. 37-43, (2015)