Optimizationofair gap clearance in 750 kV converter station area on AC side of ±800 kV UHVDC project

被引:0
|
作者
China Electric Power Research Institute, Haidian District, Beijing [1 ]
100192, China
机构
来源
Dianwang Jishu | / 10卷 / 2935-2940期
关键词
Power converters;
D O I
10.13335/j.1000-3673.pst.2015.10.038
中图分类号
TM75 [线路及杆塔];
学科分类号
摘要
When AC side of converter transformer was connected to 750 kV system, air clearance of AC side would be one of controlling factors in design of valve hall. In order to determine minimum inter-phase clearance A2 on 750 kV AC side in Lingzhou converter station, monographic studies were performed on selection method and optimal value of A2, consideringactual conditions of the station. Based on theoretical analysis and previous testing curves, A2 could be 7.0 m and 6.5 m respectively for two-bundled conductors and bus tubes. Full size tests were carried out for conductor configuration of two bundled conductors and bus tube and 50% switching impulse discharge voltage curve was obtained. According tofull size testresults, A2 could be 6.5m. Based on overvoltage level on 750 kV AC side and optimization of MOA performance, A2 could be further optimized from 6.5 m to 5.9 m or 5.8 m or even lower. These results are important for reducing valve hall size, lowering project design difficulty and saving building cost. ©, 2015, Power System Technology Press. All right reserved.
引用
收藏
相关论文
共 50 条
  • [1] 750 kV AC filter insulation coordination in UHVDC converter station
    Nie, Dingzhen
    Zhang, Tao
    Yu, Shifeng
    Gaodianya Jishu/High Voltage Engineering, 2014, 40 (06): : 1802 - 1808
  • [2] Study on clearance optimisation and altitude correction of 750 kV AC side for UHVDC converter transformer
    Ding, Yujian
    Yao, Xiuyuan
    Gu, Chen
    Wang, Xi
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2480 - 2483
  • [3] Electromagnetic Interference Prediction of ±800 kV UHVDC Converter Station
    Sun, Haifeng
    Cui, Xiang
    Du, Linsen
    IEEE TRANSACTIONS ON MAGNETICS, 2016, 52 (03)
  • [4] Simulation analysis on EMI of +/-800-kV UHVDC converter station
    Yu, Zhanqing
    He, Jinliang
    Zeng, Rong
    Zhang, Bo
    Chen, Shuiming
    Rao, Hong
    Zhao, Jie
    Li, Xiaolin
    Wang, Qi
    2007 IEEE INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY: WORKSHOP AND TUTORIAL NOTES, VOLS 1-3, 2007, : 1288 - +
  • [5] Air clearance design for valve hall of Zhexi ±800 kV UHVDC converter station using parameter g
    Chen, Xi-Lei
    Zhou, Hao
    Wang, Dong-Ju
    Shen, Yang
    Qian, Feng
    Zhou, Zhi-Chao
    Gaodianya Jishu/High Voltage Engineering, 2011, 37 (09): : 2185 - 2189
  • [6] Characteristics of EMD source Caused by valves in ±800-kV UHVDC Converter Station
    Zhao, Jie
    Yu, Zhanqing
    He, Jinliang
    Zeng, Rong
    Rao, Hong
    Li, Xiaolin
    Huang, Ying
    2009 20TH INTERNATIONAL ZURICH SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY, 2009, : 329 - +
  • [7] The Arrester Protection Study for Valve Side of Highest Potential Converter Transformer in ±800kV UHVDC Project
    Zhou Xiaoqin
    Lv Jinzhuang
    Gou Ruifeng
    Zhao Jie
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 80 - +
  • [8] Simulation Analysis on Conducted EMD Caused by Valves in ±800 kv UHVDC Converter Station
    Yu, Zhan-Qing
    He, Jin-Liang
    Zeng, Rong
    Rao, Hong
    Li, Xiao-Lin
    Wang, Qi
    Zhang, Bo
    Chen, Shui-Ming
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2009, 51 (02) : 236 - 244
  • [9] Research on overvoltage and minimum air clearance on 1000kV AC side of converter transformer in ±1100kV Guquan converter station
    Lou Ying
    Li Zhenqiang
    Xie Liang
    Wan Lei
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 2159 - 2164
  • [10] Optimizing design on AC filters in Jinping-Sunan ±800 kV UHVDC project
    Li, Jingyan
    Zhang, Zongxin
    Wu, Fangjie
    Gaodianya Jishu/High Voltage Engineering, 2012, 38 (12): : 3224 - 3229