A study on effective length of long grounding conductor in windfarm

被引:1
|
作者
Sekioka, Shozo [1 ]
Funabashi, Toshihisa [2 ]
机构
[1] Department of Electrical and Electronic Engineering, Shonan Institute of Technology, 1-1-25, Tsujido-Nishikaigan, Fujisawa 251-8511, Japan
[2] ThinkPark Tower, 2-1-1, Ohsaki, Shinagawa-ku, Tokyo 141-6029, Japan
关键词
Lightning - Electric grounding - Approximation algorithms - Turbogenerators;
D O I
10.1541/ieejpes.129.675
中图分类号
学科分类号
摘要
This paper describes a study of grounding system of wind turbine generators in a windfarm. A horizontal grounding conductor is often used to obtain a low steady-state grounding resistance. The grounding resistance of the grounding conductor shows transient characteristics. Effective length of the grounding conductor is an important parameter to estimate peak value of lightning overvoltages on the grounding system. This paper proposes approximate formulas to investigate an influence of such parameters as soil resistivity and boundary condition of the grounding system on the effective length. © 2009 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:675 / 681
相关论文
共 50 条
  • [1] A conductor arrangement that overcomes the effective length issue in transmission line grounding
    Caetano, C. E. F.
    Lima, A. B.
    Paulino, J. O. S.
    Boaventura, W. C.
    Cardoso, E. N.
    ELECTRIC POWER SYSTEMS RESEARCH, 2018, 159 : 31 - 39
  • [2] Grounding System Design for Wind Power Generation System Considering the Effective Length of Grounding Conductor
    Sekioka, Shozo
    Funabashi, Toshihisa
    Lorentzou, Maria I.
    Hatziargyriou, Nikos D.
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2025, 20 (03) : 385 - 393
  • [3] A conductor arrangement that overcomes the effective length issue in transmission line grounding: full-scale measurements
    Caetano, C. E. F.
    Paulino, J. O. S.
    Boaventura, W. C.
    Lima, A. B.
    Lopes, I. J. S.
    Cardoso, E. N.
    2018 34TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP 2018), 2018,
  • [4] Transferred overvoltages by windfarm grounding systems
    Hatziargyriou, ND
    Lorentzou, MI
    Cotton, I
    Jenkins, N
    8TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, PROCEEDINGS, VOLS 1 AND 2, 1998, : 342 - 347
  • [5] Effective Length of Horizontal Grounding Electrode
    Juric-Grgic, Ivica
    Lucic, Rino
    Ljubicic, Dragan
    2008 INTERNATIONAL CONFERENCE ON SOFTWARE, TELECOMMUNICATIONS AND COMPUTER NETWORKS, 2008, : 46 - 49
  • [6] A STUDY ON EFFECTIVE LENGTH FOR PRACTICAL DESIGN OF GROUNDING SYSTEM IN A WIND TURBINE
    Sekioka, S.
    Funabashi, T.
    2010 30TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2010,
  • [7] Effective Length of a Single Long Horizontal Ground Conductor Buried in Homogeneous Soil
    Ahmad, W. F. Wan
    Thomas, D. W. P.
    Christopoulos, C.
    Chong, S. T.
    Jasni, J.
    Ab Kadir, M. Z. A.
    Hizam, H.
    2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3, 2009, : 1565 - +
  • [8] GROUNDING ELECTRODE CONDUCTOR
    BICKNER, WE
    EC&M-ELECTRICAL CONSTRUCTION AND MAINTENANCE, 1984, 83 (09): : 120 - 120
  • [9] Transmission line grounding arrangement that overcomes the effective length issue
    Lima, A. B.
    Paulino, J. O. S.
    Boaventura, W. C.
    Caetano, C. E. F.
    Cardoso, E. N.
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,
  • [10] Effective Length Study of Grounding Electrodes Reached by Lightning Based on Transmission Line Modelling Method
    Gazzana, Daniel S.
    Bretas, Arturo S.
    Dias, Guilherme A. D.
    Tello, Marcos
    Thomas, Dave W. P.
    Christopoulos, Christos
    2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC), 2012, : 771 - 775