Analysis and Mitigation of the Subsynchronous Oscillation in Renewable Energy System Connected to the MMC-HVDC

被引:0
|
作者
Li H. [1 ]
Xie X. [1 ]
Liu R. [2 ]
Jiang Q. [1 ]
机构
[1] State Key Laboratory of Power System Operation and Control, Department of Electrical Engineering, Tsinghua University, Haidian District, Beijing
[2] Electric Power Research Institute of State Grid Liaoning Electric Power Supply Co., Ltd., Liaoning Province, Shenyang
关键词
multilevel converter-based high voltage DC; renewable generation; subsynchronous oscillation;
D O I
10.13334/j.0258-8013.pcsee.223006
中图分类号
学科分类号
摘要
During September and October 2022, 2~6 Hz sustained oscillation occurred in a renewable energy system connected to the modular multilevel converter-based high voltage DC (MMC-HVDC) in Northern China, which caused frequent tripping of the doubly-fed induction generators (DFIGs) and equipment damages. The equivalent impedance network models are established using the field recorded data to explain the cause of the oscillation. To mitigate the oscillation, inserting the subsynchronous suppression filter in the DFIG converter control is proposed. The parameter is designed using the measured data, and then field implementation and tests are conducted. Field test results under different operating conditions validate that the proposed method can effectively mitigate the oscillation without any adverse effect on normal operation. It is confirmed the proposed scheme is easy to design and implement, providing an efficient and practical solution for similar issues. ©2024 Chin.Soc.for Elec.Eng.
引用
收藏
页码:2945 / 2954
页数:9
相关论文
共 27 条
  • [1] ZHANG Zhigang, KANG Chongqin, Challenges and prospects for constructing the new-type power system towards a carbon neutrality future[J], Proceedings of the CSEE, 42, 8, pp. 2806-2818, (2022)
  • [2] LU Jing, DONG Peng, SHI Gang, Subsynchronous oscillation and its mitigation of mmc-based HVDC with large doubly-fed induction generator-based wind farm integration[J], Proceedings of the CSEE, 35, 19, pp. 4852-4860, (2015)
  • [3] HUANG Tong, CHEN Xin, ZHANG Donghui, MMC-HVDC integrated system stability analysis and impedance optimization method with consideration of voltage feed-forward control[J], Proceedings of the CSEE, 43, 23, pp. 8987-8999, (2023)
  • [4] Ke JI, Guangfu TANG, PANG Hui, Impedance modeling and analysis of MMC-HVDC for offshore wind farm integration[J], IEEE Transactions on Power Delivery, 35, 3, pp. 1488-1501, (2020)
  • [5] SUN Kun, YAO Wei, WEN Jinyu, Mechanism and characteristics analysis of subsynchronous oscillation caused by DFIG-based wind farm integrated into grid through VSC-HVDC system[J], Proceedings of the CSEE, 38, 22, pp. 6520-6532, (2018)
  • [6] Jing LYU, CAI Xu, AMIN M, Sub‐synchronous oscillation mechanism and its suppression in MMCbased HVDC connected wind farms[J], IET Generation,Transmission & Distribution, 12, 4, pp. 1021-1029, (2018)
  • [7] ZHANG Yonggang, KLABUNDE C,, WOLTER M., Study of resonance issues between DFIG-based offshore wind farm and HVDC transmission[J], Electric Power Systems Research, 190, (2021)
  • [8] SHAO Bingbing, ZHAO Shuqiang, PEI Jikun, Subsynchronous oscillation characteristic analysis of grid-connected DDWFs via VSC-HVDC system[J], Power System Technology, 43, 9, pp. 3344-3352, (2019)
  • [9] ZHANG Xu, XIE Xiaorong, LIU Hui, Design and RTDS test of the grid-side subsynchronous damping controller[J], Proceedings of the CSEE, 38, 22, pp. 6503-6510, (2018)
  • [10] GAO Benfeng, WANG Feiyue, YU Hongyang, The suppression method of wind power sub-synchronous oscillation using static synchronous series compensator [J], Transactions of China Electrotechnical Society, 35, 6, pp. 1346-1356, (2020)