Testing, Validation, and Simulation of a Novel Economizer Damper Control Strategy to Enhance HVAC System Efficiency

被引:0
|
作者
Dharmasena, Pasidu [1 ]
Nassif, Nabil [1 ]
机构
[1] Univ Cincinnati, Dept Civil & Architectural Engn & Construct Manage, Cincinnati, OH 45220 USA
关键词
economizer damper control; fan power; statistical regression; energy simulation;
D O I
10.3390/buildings14092937
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Buildings account for over 40% of global carbon dioxide (CO2) emissions, with supply and return fans in air handling units consuming a significant portion of energy. To address this, researchers have explored innovative economizer damper control methods and identified the "split-signal" strategy, which optimizes supply airflow using a single damper as a promising approach. In this study, split-signal was further refined for practical application and energy simulation, aiming to demonstrate its effectiveness and encourage adoption in real-world building mechanical systems. Laboratory testing on chilled water variable air volume (VAV) system showed fan energy savings of 0.2-5% compared to traditional "three-coupled" control, depending on ventilation air proportions, and prevented reverse airflow. A statistical regression model, based on experimental data, was developed to predict energy savings and streamline comparisons. Energy simulations were conducted across various U.S. climate zones and revealed potential savings of 15-20% in energy use, operational costs, and CO2 emissions. With minimal financial investment, split-signal control offers a cost-effective solution to improve energy efficiency and reduce environmental impact, promoting its adoption in real-world building applications.
引用
收藏
页数:19
相关论文
共 50 条
  • [1] Simulation of a temperature adaptive control strategy for an IWSE economizer in a data center
    Durand-Estebe, Baptiste
    Le Bot, Cedric
    Mancos, Jean Nicolas
    Arquis, Eric
    APPLIED ENERGY, 2014, 134 : 45 - 56
  • [2] SIMULATION MODEL OF AUTOMATED HVAC SYSTEM CONTROL STRATEGY WITH THERMAL COMFORT AND OCCUPANCY CONSIDERATIONS
    Peng, Bo
    Hsieh, Sheng-Jen
    PROCEEDINGS OF THE ASME 12TH INTERNATIONAL MANUFACTURING SCIENCE AND ENGINEERING CONFERENCE - 2017, VOL 3, 2017,
  • [3] Control Strategy Optimization for Energy Efficiency and Comfort Management in HVAC Systems
    Yang, Rui
    Wang, Lingfeng
    2015 IEEE POWER & ENERGY SOCIETY INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE (ISGT), 2015,
  • [4] Control Strategy Optimization for Energy Efficiency and Comfort Management in HVAC Systems
    Yang, Rui
    Wang, Lingfeng
    2015 IEEE POWER & ENERGY SOCIETY INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE (ISGT), 2015,
  • [5] Simulation modeling and experimental validation of generator control strategy in DFIG system
    Song, Seung-Ho
    Im, Ji-Hoon
    Choi, Hyeong-Jin
    Jeong, Seung-Gi
    Jeong, Byoung-Chang
    APEC 2007: TWENTY-SECOND ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION, VOLS 1 AND 2, 2007, : 1329 - 1333
  • [6] Modeling, Testing, and Validation of an Eddy Current Damper for Structural Vibration Control
    Huang, Z. W.
    Hua, X. G.
    Chen, Z. Q.
    Niu, H. W.
    JOURNAL OF AEROSPACE ENGINEERING, 2018, 31 (05)
  • [7] Experimental validation of a novel magnetorheological damper with an internal pressure control
    Golinelli, Nicola
    Spaggiari, Andrea
    JOURNAL OF INTELLIGENT MATERIAL SYSTEMS AND STRUCTURES, 2017, 28 (18) : 2489 - 2499
  • [8] Optimal Control Strategy for HVAC System in Building Energy Management
    Yang, Rui
    Wang, Lingfeng
    2012 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2012,
  • [9] An innovative HVAC control system: Implementation and testing in a vehicular cabin
    Fojtlin, Milos
    Fiser, Jan
    Pokorny, Jan
    Povalac, Ales
    Urbanecb, Tomas
    Jicha, Miroslav
    JOURNAL OF THERMAL BIOLOGY, 2017, 70 : 64 - 68
  • [10] Development and testing of a prototype tool for HVAC control system commissioning
    Haves, P
    Jorgensen, DR
    Salsbury, TI
    Dexter, AL
    ASHRAE TRANSACTIONS 1996, VOL 102, PT 1, 1996, 102 : 467 - 475