Experimental study on CO 2 air source heat pump water heater

被引:2
|
作者
Chen Q. [1 ]
Tong Y. [1 ]
Zhu Z.-J. [1 ]
Tang L.-M. [1 ]
Chen G.-M. [1 ]
Li J.-J. [2 ]
机构
[1] Institute of Refrigeration and Cryogenics, Zhejiang University
[2] Zhejiang Dunan Artificial Environment Limited Company
来源
Chen, G.-M. (gmchen@zju.edu.cn) | 1600年 / Zhejiang University卷 / 46期
关键词
Air source heat pump; System performance; Transcritical cycle;
D O I
10.3785/j.issn.1008-973X.2012.04.006
中图分类号
学科分类号
摘要
A prototype of heat pump was developed in order to analyze the effects of outside factors on transcritical CO 2 heat pump system performance. The system performance was investigated by changing volume flow rate or inlet temperature of cooling water, and ambient temperature. Trends of systematic parameters such as CO 2 mass flow rate, pressure ratio, heating capacity and heating coefficient of performance (COP h) were analyzed. The effects of compressor isentropic efficiency and heat transfer effectiveness of gas cooler on COP h were considered. The experimental results for the test conditions showed that CO 2 mass flow rate, pressure ratio and compressor power consumption reduced, heat capacity and COP h increased when cooling water volume flow rate increased or inlet temperature decreased. When ambient temperature increased, CO 2 mass flow rate and heat capacity had an increase, pressure ratio and compressor power consumption were almost same, and COP h increased. The compressor isentropic efficiency and heat transfer effectiveness of gas cooler were two key factors to increase COP h.
引用
收藏
页码:610 / 615
页数:5
相关论文
共 11 条
  • [1] Kim M.H., Pettersen J., Bullard C.W., Fundamental process and system design issues in CO <sub>2</sub> vapor compression systems, Progress in Energy and Combustion Science, 30, 2, pp. 119-174, (2004)
  • [2] Lorentzen G., Revival of carbon dioxide as a refrigerant, International Journal of Refrigeration, 17, 5, pp. 5-14, (1994)
  • [3] Petter N., Havard R., Reza Z., Et al., CO <sub>2</sub>-heat pump water heater: Characteristics, system design and experimental results, International Journal of Refrigeration, 21, 3, pp. 172-179, (1998)
  • [4] Pettersen J., Hafner A., Skaugen G., Development of compact heat exchangers for CO <sub>2</sub> air-conditioning systems, International Journal of Refrigeration, 21, 3, pp. 180-193, (1998)
  • [5] Chang Y.P., Pega H., CO <sub>2</sub> flow condensation heat transfer and pressure drop in multi-port microchannels at low temperatures, Inter national Journal of Refrigeration, 32, 6, pp. 1129-1139, (2009)
  • [6] Richter M.R., Song J.M., Kim M.H., Et al., Experimental results of transcritical CO <sub>2</sub> heat pump for residential application, Energy, 28, 10, pp. 1005-1019, (2003)
  • [7] Liu S.-C., Ma Y.-T., Liu Q.-J., Experiments of CO <sub>2</sub> heat pump water heater, Journal of Tianjin University, 41, 2, pp. 238-242, (2008)
  • [8] Wang D., Huang X.-Q., Zhong J.-S., Et al., Influence of the water tank temperature to the performance of C0 <sub>2</sub> heat pump water heater, Fluid Machinery, 37, 12, pp. 58-62, (2009)
  • [9] Moffat R.J., Describing the uncertainties in experimental results, Experimental Thermal and Fluid Science, 1, 1, pp. 3-17, (1988)
  • [10] Holman J.P., Experimental Methods for Engineers, pp. 41-53, (1989)