Diagnostic Criterion of Turn-to-turn Overvoltage Test in Dry-type Air-core Reactor

被引:0
|
作者
Guo S. [1 ]
Niu Z. [1 ]
Li H. [1 ]
Mao T. [2 ]
Ma J. [1 ]
Long K. [1 ]
机构
[1] Electric Power Research Institute of State Grid Jibei Electric Power Company, Beijing
[2] State Grid Jibei Electric Power Company, Beijing
来源
关键词
Attenuation coefficient; Dry-type air-core reactor; Quantitative criterion; Turn-to-turn insulation; Turn-to-turn overvoltage;
D O I
10.13336/j.1003-6520.hve.20180301018
中图分类号
学科分类号
摘要
Turn-to-turn insulation defects in dry-type air-core reactors are the main cause of equipment failure. Consequently, we proposed the diagnostic criteria based on oscillation frequency, attenuation coefficient, and standard deviation. For oscillation frequency, if the frequency deviation of the rated voltage and the test voltage is more than 2%, the reactor has a turn-to-turn insulation defect and is in a serious state. If the deviation is between 2% and 1%, the reactor may have turn-to-turn insulation defects and is in an attendant state. If the deviation does not exceed 1%, the reactor is in a normal state. For attenuation coefficient, two criteria such as 5% and 10% are established. For standard deviation, two criteria such as 10% and 30% are established. A standardized judgment flow can be used to assess the turn-to-turn insulation of dry-type air-core reactor, which provides a reference for the operation and maintenance of the reactor equipment. © 2018, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:804 / 811
页数:7
相关论文
共 20 条
  • [1] Wang G., Li Y., Yang S., Failure analysis and preventive measures to dry-type air-core reactor, Power Capacitor & Reactive Power Compensation, 36, 6, pp. 82-85, (2015)
  • [2] Xu L., Fault analysis of dry-type air-core series reactor, Power Capacitor & Reactive Power Compensation, 29, 2, pp. 50-54, (2008)
  • [3] Zhang M., Wang G., Zhang Y., Et al., Insulation design and test analysis of ±1100 kV UHV dry-type smoothing reactor, High Voltage Engineering, 41, 5, pp. 1760-1768, (2015)
  • [4] Zhang B., Zhao K., Zou J., Calculation and analysis of lighting overvoltage for foil-wound air-core reactors, High Voltage Engineering, 42, 2, pp. 666-672, (2016)
  • [5] Yu Z., Wang S., Optimum design of dry-type air-core reactor based on coupled multi-physics of reconstructed finite element model, Transactions of China Electrotechnical Society, 30, 20, pp. 71-78, (2015)
  • [6] Jiang Z., Wen X., Wang Y., Et al., Test and coupling calculation of temperature field for UHV dry-type air-core smoothing reactor, Proceedings of the CSEE, 35, 20, pp. 5344-5350, (2015)
  • [7] Liao M., Cheng X., Zhai Y., Simulation and experiment on impulse oscillating turn-to-turn insulation test system of dry-type air core reactor, High Voltage Engineering, 37, 6, pp. 1343-1348, (2011)
  • [8] Chen Q., Qiu Y., Wei X., Et al., Pulse voltage resonance method for detecting turn to turn insulation defects in air core reactor, Transactions of China Electrotechnical Society, 14, 6, pp. 55-58, (1999)
  • [9] Jiang S., Dai R., Xia X., Et al., Principle and analysis on inter-turn insulation detection of dry-type air-core reactor, High Voltage Apparatus, 47, 6, pp. 67-71, (2011)
  • [10] Gou X., Liu X., Yang H., Et al., Simulation study of the influence of turn-to-turn insulation fault on inductance of dry-type air-core reactors, High Voltage Apparatus, 51, 10, pp. 117-121, (2015)