Fault Line Selection in Resonant Earthed System Based on Morphological Peak-Valley Detection

被引:0
|
作者
Shu H. [1 ]
Huang H. [1 ]
Tian X. [1 ]
Dong J. [2 ]
Huang R. [3 ]
机构
[1] Faculty of Electric Power Engineering, Kunming University of Science and Technology, Kunming
[2] School of Electrical Engineering and Automation, Harbin Institute of Technology, Harbin
[3] Power Science Research Institute of Yunnan Power Grid Co. Ltd., Kunming
基金
中国国家自然科学基金;
关键词
Fault line selection; Feature band; Mathematical morphology; Peak-valley detection; Resonant earthed system; Transient component;
D O I
10.7500/AEPS20180506005
中图分类号
学科分类号
摘要
Transient electrical quantity information is very abundant when single-phase grounding fault occurs in resonant earthed system. The short window data of 1/4 period of zero sequence current fault of each line are transformed by wavelet transform. The frequency band of power frequency is eliminated and the feature frequency band is selected according to the principle of maximum energy sum. The reconstructed wavelet coefficients under the feature frequency band are checked by morphological peak-valley detection.The peak-valley characteristic of the fault feeder is opposite to that of the total feeders, which is used as the fault line selection criterion. The simulation analysis and practical verification demonstrate the feasibility and effectivity of this method. © 2019 Automation of Electric Power Systems Press.
引用
收藏
页码:228 / 233
页数:5
相关论文
共 17 条
  • [1] Xue Y., Feng Z., Xu B., Et al., Earth fault protection in non-solidly earthed network based on transient zero sequence current comparison, Automation of Electric Power Systems, 27, 9, pp. 48-53, (2003)
  • [2] Shu H., Duan R., Zhu M., Et al., An ANN method of faulted feeder detection based on continuous wavelet transform coefficients'RMS values of zero sequence current, Journal of Electric Power Science and Technology, 28, 1, pp. 17-24, (2013)
  • [3] Tang J.R., Yin X.G., Wen M.H., Et al., Fault location in neutral non-effectively grounded distribution systems using phase current and line-to-line voltage, Electric Power Components and Systems, 42, 13, pp. 1371-1385, (2014)
  • [4] Liu J., Zhang X., Shen W., Et al., Performance testing of single phase to earth fault location for distribution network with neutral point non-effectively grounded systems, Automation of Electric Power Systems, 42, 1, pp. 138-143, (2018)
  • [5] Tang T., Huang C., Jiang Y., Et al., Fault line selection method in resonant earthed system based on transient signal correlation analysis under high and low frequencies, Automation of Electric Power Systems, 40, 16, pp. 105-111, (2016)
  • [6] Qu Y., Tan W., Yang Y., A new transient method for earth fault line selection in resonant grounded power system based on morphological filtering, Automation of Electric Power Systems, 32, 12, pp. 73-77, (2008)
  • [7] Zhang Y., Wang Q., New method for single phase to ground fault feeder selection based on analysis of fault transient characteristics, Automation of Electric Power Systems, 33, 16, pp. 76-80, (2009)
  • [8] Zhou D., Liu Z., Hu F., Et al., A new method for fault line selection based on wavelet de-noising and transient current energy grouping comparison in ineffective grounding system, Power System Protection and Control, 38, 7, pp. 22-28, (2010)
  • [9] Shu H., Peng S., Faulty line detection by relative energy method for hybrid transmission lines, Electric Power Automation Equipment, 29, 11, pp. 1-5, (2009)
  • [10] Zhang J., He Z., Jia Y., Fault line identification approach based on S-transform, Proceedings of the CSEE, 31, 10, pp. 109-155, (2011)