A fault diagnosis method for the secondary circuits of protection systems in smart substations based on improved D-S evidence theory

被引:0
|
作者
Dai Z. [1 ]
Lu H. [1 ]
Liu Y. [1 ]
Liu B. [1 ]
Chen Y. [2 ]
机构
[1] Department of Electrical Engineering, North China Electric Power University, Baoding
[2] Electric Power Research Institute of Yunnan Power Grid Co., Ltd., Kunming
基金
中国国家自然科学基金;
关键词
Fault diagnosis; Fault proof table; Relay protection; Secondary circuit; Smart substation;
D O I
10.19783/j.cnki.pspc.190722
中图分类号
学科分类号
摘要
In smart substations, it is difficult to identify the faulty component quickly and effectively in the secondary circuit of protection systems. In view of this, a fault diagnosis method for secondary circuits of protection systems in smart substations is proposed to find faulty components accurately. First, the physical-loop and virtual-loop models of the secondary circuit are established according to the SCD file, and their mapping relationship is implemented. Secondly, a fault proof table is used to obtain the suspicious fault component set in secondary circuits of protection systems. Then, improved D-S evidence theory is proposed to evaluate the components in the suspicious component set, and the probability of secondary circuit failure caused by each component is obtained for the realization of fault component identification. Finally, case studies demonstrate that the proposed method can deal with excessive conflict of component self-checking evidence, find fault component accurately, and supply reference for the operation and maintenance of protection systems. © 2020, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:59 / 67
页数:8
相关论文
共 29 条
  • [1] (2007)
  • [2] (2010)
  • [3] SWAGATA D, SUNDARAVARADAN A, SURYA S., Relay performance verification using fault event records, Protection and Control of Modern Power Systems, 3, 3, pp. 226-235, (2018)
  • [4] WANG Youyuan, CAI Yanan, WANG Can, Et al., Intelligent diagnosis system for substation equipment based on cloud platform, High Voltage Engineering, 41, 12, pp. 3895-3901, (2015)
  • [5] YE Yuanbo, XIE Min, WANG Jiaqi, Et al., Real time reliability analysis of relay protection system in intelligent substation based on Markov model and GO method, Power System Protection and Control, 47, 2, pp. 47-55, (2019)
  • [6] LI Ruisheng, LI Yanbin, ZHOU Fengquan, Et al., Every week right smart substation functional architecture and design principles, Power System Protection and Control, 38, 21, pp. 24-27, (2010)
  • [7] GAO Lei, YANG Yi, LIU Yu, Et al., Proof table based fault location method for process level channel in smart substations, Automation of Electric Power Systems, 39, 4, pp. 147-151, (2015)
  • [8] DONG Huaipu, WANG Weijie, LIU Wenbiao, Et al., Fault diagnosis technology of secondary virtual loop and physical fiberloop fusion based on depth first search, Electric Power Automation Equipment, 39, 5, pp. 219-223, (2019)
  • [9] ZHOU Hongyang, HUANG Jiayin, ZHANG Chi, Et al., Petri net based fault diagnosis for GOOSE circuits of smart substation, Southern Power System Technology, 11, 6, pp. 49-56, (2017)
  • [10] NIE Dezhen, Research on secondary system fault diagnosis method in intelligent substation, (2014)