VSG control based on adaptive Terminal sliding-mode control method

被引:0
|
作者
Yan B. [1 ]
Wang B. [1 ]
机构
[1] School of Automation, Nanjing University of Science and Technology, Nanjing
关键词
Grid-connected inverter; Robustness; Stability; Terminal sliding-mode control; Virtual synchronous generator;
D O I
10.16081/j.issn.1006-6047.2018.10.022
中图分类号
学科分类号
摘要
The low inertia and under-damping characteristics of the inverter-dominated distributed generation unit may impact the power system stability. Using the fourth-order synchronous generator model with the excitation and valve comprehensive control, a virtual synchronous generator control scheme based on adaptive Terminal sliding-mode control is designed. Two nonsingular Terminal sliding-mode functions are constructed based on the two input variables of the system. The convergence of the error is fast owing to the nonlinear Terminal sliding-mode function. As a consequence, the control effectiveness of the designed controller can be ensured. The simulative results show that the proposed control strategy can provide sufficient inertia and damping to guarantee the robustness of system in the presence of uncertain parameters and external disturbances, which can further suppress the system oscillation and improve the power system stability. © 2018, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:140 / 146
页数:6
相关论文
共 18 条
  • [1] Yang X., Su J., Lu Z., Et al., Overview on micro-grid technology, Proceedings of the CSEE, 34, 1, pp. 57-70, (2014)
  • [2] Zhou X., Chen S., Lu Z., Review and prospect for power system development and related technologies: a concept of three-generation power systems, Proceedings of the CSEE, 33, 22, pp. 1-11, (2013)
  • [3] Li D., Zhu Q., Cheng Y., Et al., Control strategy of virtual synchronous generator based on self-adaptive rotor inertia and damping combination control algorithm, Electric Power Automation Equipment, 37, 11, pp. 72-77, (2017)
  • [4] Chen Y., Hesse R., Turschner D., Et al., Improving the grid power quality using virtual synchronous machines, International Conference on Power Engineering, Energy and Electrical Drives, pp. 1-6, (2011)
  • [5] Tom L., Participation of inverter-connected distributed energy resources in grid voltage control, (2011)
  • [6] Xiao X., Chen M., Power control of virtual synchronous generator under unbalanced grid voltage, Electric Power Automation Equipment, 37, 8, pp. 193-200, (2017)
  • [7] Hirase Y., Abe K., Sugimoto K., Et al., A grid connected inverter with virtual synchronous generator model of algebraic type, IEEE Transactions on Power and Energy, 132, 4, pp. 371-380, (2012)
  • [8] Lu Z., Sheng W., Zhong Q., Et al., Virtual synchronous generator and its application in micro-grid, Proceedings of the CSEE, 34, 16, pp. 2591-2603, (2014)
  • [9] Liu F., Cao W., Yu Y., Research on Virtual Synchronous Generator(VSG) technology, Electrical Engineering, pp. 1-8, (2014)
  • [10] Tian Y., Zheng T., The frequency control of virtual synchronous generator based on adaptive adjusting, Southern Power System Technology, 8, 5, pp. 76-79, (2014)