摘要
To increase the operation speed of relays under the outgoing line fault conditions, this paper proposed a high-speed operation strategy based on the low-frequency transient component. The proposed method consists of two parts: the high-speed directional element and the fast outgoing line fault detection element. The measurement voltage drop and calculation voltage drop on the system equivalent impedance from relay location to backside equivalent power sources are introduced to detect the fault direction. By comparing the integration of the absolute values of residual voltage and setting voltage during a short time after the fault, the outgoing fault can be detected rapidly. The main advantage of the proposed method is its high reliability, because this method would not be affected by the high-frequency component. To overcome the impact of the capacitor voltage transformer transient characteristics on the outgoing line fault detection element, an effective method based on equal transfer processes is also presented. Finally, an extensive performance evaluation using PSCAD/EMTDC simulation corroborates the effectiveness of the proposed method. Simulation results show that the proposed method has the high operation speed under the outgoing line fault conditions. © 2020, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:2415 / 2426
页数:11
相关论文
共 26 条
  • [1] Suonan Jiale, Liu Wentao, Chen Yong, Et al., Adaptive distance protection based on R-L model error, Automation of Electric Power Systems, 30, 22, pp. 66-72, (2006)
  • [2] K K Li K K Li, Zhang Yanxia, Study of adaptive window length algorithm based on linear differential equation, Proceedings of the CSEE, 20, 7, pp. 25-28, (2000)
  • [3] Chen Xuewei, Gao Houlei, Xiang Minjiang, Et al., Improved R-L model distance protection algorithm based on differential output of electronic transducers, Transactions of China Electrotechnical Society, 29, 6, pp. 283-289, (2014)
  • [4] (2014)
  • [5] Wen Minghao, Chen Deshu, Yin Xianggen, Fast distance protection of EHV transmission lines based on equal transfer processes, Proceedings of the CSEE, 32, 4, pp. 145-150, (2012)
  • [6] CSC-103A-G数字式超高压线路保护装置说明书, (2013)
  • [7] Dong Xinzhou, Luo Shuxin, Shi Shenxing, Et al., PCTDR-based directional comparison pilot protection technology and its application in 750kV transmission lines, Electric Power Automation Equipment, 35, 9, pp. 1-5, (2015)
  • [8] Duan Jiandong, Zhang Baohui, Zhou Yi, Study of ultra-high-speed transient-based directional relay, Proceedings of the CSEE, 25, 4, pp. 7-12, (2005)
  • [9] Zou Guibin, Gao Houlei, Jiang Shifang, Et al., Novel transient travelling wave based amplitude comparison ultra high speed directional protection, Proceedings of the CSEE, 29, 7, pp. 84-90, (2009)
  • [10] Dong Xinzhou, Ge Yaozhong, He Jiali, Surge impedance relay, IEEE Transactions on Power Delivery, 20, 2, pp. 1247-1256, (2005)