Dead-Time Effect and Background Grid-Voltage Harmonic Suppression Methods for Inverters with Virtual Impedance Control

被引:0
|
作者
Chen J. [1 ]
Zhang X. [1 ]
Yan Z. [1 ]
Wei Z. [2 ]
Chen X. [1 ]
机构
[1] Jiangsu Key Laboratory of New Energy Generation and Power Conversion, Nanjing University of Aeronautics & Astronautics, Nanjing
[2] NARI Group Corporation/State Grid Electric Power Research Institute, Nanjing
关键词
Dead-time compensation; Grid-voltage background harmonics; Indirect-current-controlled inverter (ICCI); Virtual impedance;
D O I
10.19595/j.cnki.1000-6753.tces.200073
中图分类号
学科分类号
摘要
Grid-connected inverters, as the interface between distributed energy and large power grids, have high requirements in terms of control structure and power quality. Inverters with indirect- current-control has fast power response and can realize the smooth transfer between grid-connected and stand-alone modes. In this paper, the grid-connected current distortion caused by the dead-time effect of the semiconductor devices and the grid-voltage background harmonics are analyzed. Furthermore, specific solutions by adding virtual parallel and series impedance are given to improve the power quality. Simulation and experiments verify the effectiveness of the proposed method. © 2021, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:1671 / 1680
页数:9
相关论文
共 18 条
  • [1] Wang Chengshan, Li Peng, Development and challenges of distributed generation, the micro-grid and smart distribution system, Automation of Electric Power Systems, 34, 2, pp. 10-15, (2010)
  • [2] Wen Juan, Tan Yanghong, He Yigang, Et al., A multi-stage service restoration method for complex distribution networks with distributed generators, Transactions of China Electrotechnical Society, 33, 14, pp. 3332-3341, (2018)
  • [3] Faisal A M, Heikki N K., System modelling and online optimal management of microgrid using multi- objective optimization, IEEE International Conference on Clean Electrical Power, pp. 148-153, (2007)
  • [4] Shi Rongliang, Wang Chengshan, Zhang Xing, Et al., A control strategy for islanded photovoltaic-battery- diesel microgrid based on virtual synchronous generator, Transactions of China Electrotechnical Society, 32, 23, pp. 127-139, (2017)
  • [5] Rocabert J, Luna A, Blaabjerg F, Et al., Control of power converters in AC microgrids, IEEE Transa- ctions on Power Electronics, 27, 11, pp. 4734-4749, (2012)
  • [6] Du Yan, Su Jianhui, Zhang Liuchen, Et al., A droop control method for improving load distribution in an island microgrid, Automation of Electric Power Systems, 39, 15, pp. 24-29, (2015)
  • [7] Kim H, Yu T, Choi S., Indirect current control algorithm for utility interactive inverters in distri- buted generation systems, IEEE Transactions on Power Electronics, 23, 3, pp. 1342-1347, (2008)
  • [8] Park S, Kwon M, Choi S., A new anti-islanding method for indirect current control of grid connected inverter, IEEE 3rd International Future Energy Electronics Conference and ECCE Asia, pp. 1230-1234, (2017)
  • [9] Zhao Guopeng, Han Minxiao, Liu Jinjun, Et al., Design of parameters in static synchronous com- pensator with indirect current control based on the system stability, Transactions of China Electro- technical Society, 27, 9, pp. 17-24, (2012)
  • [10] Guo Liang, Xu Aiguo, Xie Shaojun, Et al., Research on indirect current control algorithm for grid- connected inverter, Power Electronics, 42, 4, pp. 36-38, (2008)