HYBRID ISLANDING DETECTION METHOD BASED ON RATE OF CHANGE OF RESISTANCE AND ACTIVE POWER

被引:0
|
作者
Gao S. [1 ,2 ]
Guo F. [1 ,2 ]
Shao M. [3 ]
Han Y. [4 ]
机构
[1] College of Electrical and Control Engineering, Xi’an University of Science and Technology, Xi’an
[2] Xi’an Key Laboratory of Electrical Equipment Condition Monitoring and Power Supply Security, Xi’an
[3] State Grid Shaanxi Electric Power Research Institute, Xi’an
[4] Ningbo Power Supply Company, State Grid Zhejiang Electric Power Co.,Ltd., Ningbo
来源
关键词
active power disturbance; distributed power generation; fault detection; hybrid islanding detection method; power quality;
D O I
10.19912/j.0254-0096.tynxb.2023-0064
中图分类号
学科分类号
摘要
In order to solve the problem that the traditional detection method is difficult to set the threshold and has great influence on power quality,a hybrid islanding detection method based on the combination of resistance change rate and active power disturbance is proposed. As a passive method,the resistance change rate can respond quickly after islanding, and the active power disturbance module is turned on only when the passive method suspects islanding,and the minimum active power that can make the voltage of the common coupling point exceed the limit is injected adaptively. The simulation results show that this method can quickly and correctly detect the islanding effect,and there will be no misjudgment even in the case of non-islanding. © 2024 Science Press. All rights reserved.
引用
收藏
页码:324 / 332
页数:8
相关论文
共 32 条
  • [1] GAO S P, WANG K C, LI W H., A new islanding detection method for grid-connected photovoltaic system based on harmonic impedance component [J], Acta energiae solaris sinica, 39, 5, pp. 1335-1341, (2018)
  • [2] FENG X P, SONG X H, LIANG Y,, Et al., Islanding method based on minimum spanning tree and improved genetic algorithm for distribution system with DGs[J], High voltage engineering, 41, 10, pp. 3470-3478, (2015)
  • [3] LONG X., Research on islanding’s characteristics and anti-islanding strategy of grid- connected photovoltaic power generation system[D], (2018)
  • [4] WU S J, YUAN X D, Et al., Anti- islanding detection standards for distributed PV power generations and analysis on factors influencing non- detection zone of islanded PV generation[J], Power system technology, 39, 4, pp. 924-931, (2015)
  • [5] WU Y Q,, MA X, YE Y Q,, Et al., Hybrid islanding detection strategy suitable for different operating conditions of multi- control inverters[J], High voltage engineering, 46, 11, pp. 3887-3895, (2020)
  • [6] SUN Z A, YANG Z L, WANG Y B, Et al., A hybrid islanding detection method for distributed multi- inverter systems[J], Proceedings of the CSEE, 36, 13, pp. 3590-3597, (2016)
  • [7] YU K,, YONG J,, LIANG S B, Et al., An improved power line signaling technique based anti- islanding protection approach for distributed generation system[J], Proceedings of the CSEE, 35, 13, pp. 3283-3291, (2015)
  • [8] JIA K, ZHU Z X,, YANG Z,, Et al., Intelligent islanding detection method for grid-connected photovoltaic power system based on improved Adaboost algorithm[J], Power system technology, 43, 4, pp. 1227-1238, (2019)
  • [9] ZHANG Y,, Et al., Evaluation of anti-islanding schemes based on nondetection zone concept [C], IEEE 34th Annual Conference on Power Electronics Specialist,2003. PESC’03, pp. 1735-1741, (2003)
  • [10] WU Q Y,, WU C Y,, Et al., Islanding detection of grid-connected PV system based on bi-direction voltage harmonic variation[J], Electric power automation equipment, 39, 3, pp. 194-199, (2019)