Mechanism and Characteristics of Subsynchronous Oscillation Caused by LVRT in Offshore Direct Drive Wind Farm With Weak Connection

被引:0
|
作者
Wang Y. [1 ]
Zhang Z. [1 ]
Tang H. [1 ]
Lin Y. [2 ]
Xue J. [2 ]
Xue A. [1 ]
机构
[1] State Key Laboratory of Alternate Electrical Power System With Renewable Energy Source, North China Electric Power University, Changping District, Beijing
[2] Institute of Economic and Technology, State Grid Fujian Electric Power Co., Ltd., Fujian Province, Fuzhou
来源
关键词
direct drive wind farm; intermittent saturation; low voltage ride-through; switched oscillation;
D O I
10.13335/j.1000-3673.pst.2023.0959
中图分类号
学科分类号
摘要
Offshore wind farms must have low voltage ride-through (LVRT) capability to avoid wind turbine disconnection in case of failure. However, the impact of LVRT strategy on the stability of grid-connected systems after large disturbances is unknown. Because of this, the equivalent model of PMSGs interfaced with the AC power grid is established. Meanwhile, the mechanism and characteristics of different types of oscillation caused by LVRT under large disturbance when the connection is weak are analyzed in this paper. The details are as follows: Firstly, the electromagnetic transient model of an offshore direct-driven wind farm with LVRT is built. Secondly, the impedance characteristics of the system are analyzed, which shows that the system is at risk of subsynchronous oscillation. After the positive damping system with a weak connection is subject to large disturbance, a subsynchronous frequency band oscillation will be formed by LVRT participation. Thirdly, the relationship between the oscillation and different control principles of LVRT is explored, which shows that strategy 1 or 2 of the stage 2-1 in a reactive link of LVRT for a system with positive damping after a large disturbance can participate in the formation of switched oscillation caused by excessive compensation current, and the phenomenon that intermittent saturation of limit exists in the oscillations corresponding to both control strategies. Finally, the influence of LVRT control parameters or strategies on the oscillation characteristics is analyzed. © 2024 Power System Technology Press. All rights reserved.
引用
收藏
页码:2902 / 2909
页数:7
相关论文
共 17 条
  • [1] WANG Desheng, YAN Xiangwu, JIA Jiaoxin, High/low voltage continuous fault ride through strategy of PMSGs based on virtual synchronization technology[J], Proceedings of the CSEE, 42, 6, pp. 2164-2174, (2022)
  • [2] ZHOU Yingkun, XIE Heng, SUN Huadong, Influence of renewable energy low voltage ride-through control parameters on overvoltage[J], Power System Technology, 46, 5, pp. 1907-1916, (2022)
  • [3] WANG Shiwen, LIU Fei, LIU Qinyi, Low-voltage riding-through control strategy for two-staged grid-connected photovoltaic system under asymmetrical faults[J], Power System Technology, 47, 1, pp. 91-102, (2023)
  • [4] Jianxun JIN, YANG Ruohuan, ZHANG Runtao, Combined low voltage ride through and power smoothing control for DFIG/PMSG hybrid wind energy conversion system employing a SMES-based AC-DC unified power quality conditioner[J], International Journal of Electrical Power & Energy Systems, 128, (2021)
  • [5] HAN Ji, Combined re/active power control for wind farm under low voltage ride through based on wind turbines grouping and deep reinforcement learning[J], Proceedings of the CSEE, 43, 11, pp. 4228-4243, (2023)
  • [6] LI Mingjie, Zhao YU, XU Tao, Study of complex oscillation caused by renewable energy integration and its solution[J], Power System Technology, 41, 4, pp. 1035-1042, (2017)
  • [7] ZHANG Jianyun, Research on the mechanism of subsynchronous oscillations of wind farms in Hami[J], Proceedings of the CSEE, 38, 18, pp. 5447-5460, (2018)
  • [8] WU Linlin, ZHAO Wei, XU Man, Mechanism analysis and suppression of repeated voltage fluctuation considering fault ride through characteristics of the wind turbine[J], Journal of Global Energy Interconnection, 5, 3, pp. 290-297, (2022)
  • [9] XUE Ancheng, FU Xiaoyu, QIAO Dengke, Review and prospect of research on sub-synchronous oscillation mechanism for power system with wind power participation[J], Electric Power Automation Equipment, 40, 9, pp. 118-128, (2020)
  • [10] XIE Xiaorong, LIU Huakun, HE Jingbo, Mechanism and characteristics of subsynchronous oscillation caused by the interaction between full-converter wind turbines and AC systems[J], Proceedings of the CSEE, 36, 9, pp. 2366-2372, (2016)