Adaptive separation method of vibration and motor current signal of vacuum on-load tap-changer for converter transformer

被引:0
|
作者
He L. [1 ]
Ding D. [1 ]
Li X. [2 ]
Yuan M. [1 ]
Zhang Z. [1 ]
Liu W. [3 ]
机构
[1] Sichuan Energy Internet Research Institute Tsinghua University, Chengdu
[2] Shanghai Humming Electric Equipment Manufacturing Co., Ltd., Shanghai
[3] Department of Electrical Engineering, Tsinghua University, Beijing
关键词
adaptive separation; converter transformer; endpoint detection; motor current signal; on-load tap changer; vibration signal;
D O I
10.15938/j.emc.2023.08.008
中图分类号
学科分类号
摘要
On-load tap-changer (OLTC) is the core component of ultra high voltage (UHV) converter transformer, and the online monitoring technology based on driving motor current and vibration signal is a research hotspot for OLTC mechanical state in recent years. In order to automatically extract the vibration signal and drive motor current signal fragment from the online monitoring data of converter transformer OLTC, an adaptive separation method based on endpoint detection is studied in this paper. Firstly, the basic principle of endpoint detection method was introduced, and the separation process of vibration signal and motor current signal was proposed. Then, an OLTC online monitoring system was built and deployed in UHV converter station. Finally, the time-domain and frequency-domain characteristics of online monitoring data was analyzed, and the vibration signal and motor current signal were extracted by differential endpoint detection technology. Three working stages of the driving motor were divided according to the start and end points of the signals. The results show that the endpoint detection method adopted in this paper can effectively separate OLTC vibration and current motor signals, and the positioning error is less than 5 ms, which can provide a basis for OLTC online monitoring data analysis and fault diagnosis. © 2023 Editorial Department of Electric Machines and Control. All rights reserved.
引用
收藏
页码:73 / 79
页数:6
相关论文
共 20 条
  • [1] CHEN Fei, RAO Honglin, WU Jianbo, Introduction and fault analysis of OLTC in converter transformer, Transformer, 51, 1, (2014)
  • [2] Transformer reliability survey, (2015)
  • [3] BENGTSSON C., Status and trends in transformer monitoring[J], IEEE Transactions on Power Delivery, 11, 3, (1996)
  • [4] KANG P, BIRTWHISTLE D., Characterisation of vibration signals using continuous wavelet transform for condition assessment of on-load tap-changers, Mechanical Systems and Signal Processing, 17, 3, (2003)
  • [5] RIVAS E, BURGOS J C., Vibration analysis using envelope wavelet for detecting faults in the oltc tap selector[J], IEEE Transactions on Power Delivery, 25, 3, (2010)
  • [6] ZHANG Weizheng, SHI Linchen, JI Shengchang, Et al., Fault diagnosis of OLTC based on wavelet singularity detection[J], High Voltage Engineering, 32, 7, (2006)
  • [7] DUAN Ruochen, WANG Fenghua, Fault diagnosis of on-load tap-changer in converter transformer based on time-frequency vibration analysis[J], IEEE Transactions on Industrial Electronics, 63, 6, (2016)
  • [8] ZHANG Huifeng, MA Hongzhong, CHEN Kai, Et al., Fault diagnosis of transformer on load tap changer based on EMD-HT time frequency analysis of vibration signal [ J], High Voltage Apparatus, 48, 1, (2012)
  • [9] KYUSUNG K, PARLOS A G, MOHAN BHARADWAJ R., Sensorless fault diagnosis of induction motors, IEEE Transactions on Industrial Electronics, 50, 5, (2003)
  • [10] QIU Zhibin, RUAN Jiangjun, HUANG Daochun, Et al., Mechanical fault diagnosis of high voltage disconnector based on motor current detection [ J ], Proceedings of the CSEE, 35, 13, (2015)