Identification and Location of Cable Faults Based on Input Impedance Spectrum

被引:0
|
作者
Li R. [1 ]
Zhou K. [1 ]
Rao X. [1 ]
Xie M. [2 ]
Liang Z. [1 ]
Gong W. [1 ]
机构
[1] College of Electrical Engineering, Sichuan University, Chengdu
[2] State Grid Wuxi Power Supply Company, Wuxi
来源
Gaodianya Jishu/High Voltage Engineering | 2021年 / 47卷 / 09期
基金
中国国家自然科学基金;
关键词
Cable faults; Fault location; Fault type identification; Input impedance spectrum; Kaiser window;
D O I
10.13336/j.1003-6520.hve.20200491
中图分类号
学科分类号
摘要
In order to solve the shortcomings of impulse current experimentation (ICE) and time domain reflectometry (TDR) in the diagnosis of power cable faults, a method based on input impedance spectrum is proposed for identifying and locating cable faults. First, according to the distribution parameter model of power cables, input impedance spectrum, spectrum analysis, and Kaiser window, the basic principles were explained in detail. Then, different types of cable faults (open-circuit, short-circuit, high-resistance and low-resistance faults) were modeled and analyzed. And the input impedance spectrum characteristics of normal/fault cables were obtained by simulation. Based on this, the input impedance spectra of the faulty cables were analyzed to obtain an intuitive fault location spectrum, thereby achieving high-sensitivity location of cable faults. Finally, to test the effectiveness of the method, fault simulations were carried out on the 40 m-long coaxial cable and the 1 000 m-long 10 kV cross linked polyethylene (XLPE) power cable in the laboratory. The simulation and test results indicate that the method has a good recognition effect for the open-circuit fault and fault points with impedance in the range of 0 Ω ~ 38Z0(Z0 is the characteristic impedance of the cable), and the fault location error is less than 0.4%. Compared with ICE method and TDR method, this method is more sensitive, which can be adopted to realize the type identification and high-precision positioning of cable faults. © 2021, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:3236 / 3245
页数:9
相关论文
共 20 条
  • [1] DU Boxue, HAN Chenlei, LI Jin, Et al., Research status of polyethylene insulation for high voltage direct current cables, Transactions of China Electrotechnical Society, 34, 1, pp. 179-191, (2019)
  • [2] ZHOU Yuanxiang, ZHAO Jiankang, LIU Rui, Et al., Key technical analysis and prospect of high voltage and extra-high voltage power cable, High Voltage Engineering, 40, 9, pp. 2593-2612, (2014)
  • [3] DU Boxue, LI Zhonglei, YANG Zhuoran, Et al., Application and research progress of HVDC XLPE cables, High Voltage Engineering, 43, 2, pp. 344-354, (2017)
  • [4] YUAN Yanling, ZHOU Hao, DONG Jie, Et al., Sheath current in HV cable systems and its on-line monitoring for cable fault diagnosis, High Voltage Engineering, 41, 4, pp. 1194-1203, (2015)
  • [5] CHEN Xin, LI Wenpeng, LI Zhenyu, Et al., Prospect on key technology of the XLPE insulation materials and HVDC cables, High Voltage Engineering, 46, 5, pp. 1577-1585, (2020)
  • [6] WANG Guangzhu, JIA Chunjuan, ZHANG Libin, A novel method of fault accurate location for low voltage power cables with steel armor, Automation of Electric Power Systems, 38, 3, pp. 161-165, (2014)
  • [7] ZHANG Shu, LIN Sheng, TANG Jin, Et al., Fault location of self-clearing fault in three phase single core cables based on double impedance model, Transactions of China Electrotechnical Society, 31, 17, pp. 1-10, (2016)
  • [8] LU Honggang, QIN Jian, CHEN Xiangxun, Et al., Overview of power cable fault location, Power System Technology, 28, 20, pp. 58-63, (2004)
  • [9] ZHANG Zhengtuan, WEN Feng, XU Bingyin, Wavelet analysis based power cable fault location, Automation of Electric Power Systems, 27, 1, pp. 49-52, (2003)
  • [10] CHANG S J, LEE C K, LEE C K, Et al., Condition monitoring of instrumentation cable splices using Kalman filtering, IEEE Transactions on Instrumentation and Measurement, 64, 12, pp. 3490-3499, (2015)