Passive super-twisting second-order sliding mode control strategy for MMC-UPQC under unbalanced grid voltage

被引:0
|
作者
Huang Z.-F. [1 ]
Zhou J.-P. [1 ]
Mao D.-J. [1 ]
Qi G.-Q. [1 ]
Cong F.-P. [1 ]
机构
[1] College of Automation Engineering, Shanghai University of Electric Power, Shanghai
来源
Kongzhi yu Juece/Control and Decision | 2024年 / 39卷 / 05期
关键词
Euler-Lagrange model; modular multilevel converter; passive super-twisting second-order sliding mode control; power grid voltage imbalance; unified power quality regulator;
D O I
10.13195/j.kzyjc.2022.0964
中图分类号
学科分类号
摘要
When the voltage of the grid is unbalanced, it is difficult to use traditional control methods for the unified power quality conditioner (UPQC) of a modular multilevel converter (MMC) to comprehensively control the power quality, and the compensation efficiency and accuracy are low. To solve these problems, a passive super-twisting second-order sliding mode control strategy is proposed. Firstly, based on the mathematical model of the MMC-UPQC and passive control theory, a positive and negative sequence passive controller based on the Euler-Lagrange model under unbalanced power grid voltage is designed. Then, super-twisting second-order sliding mode control is added to improve the passive controller, which suppresses chattering of the conventional sliding mode, and solves the problem that passive control requires high precision of the system. It improves the response speed, compensation accuracy and anti-interference ability of the system, and improves the overall performance of the system. Finally, the simulation is carried out on the Matlab/Simulink platform and compared with PI control and independent passive control. Simulation results verify the effectiveness and superiority of the proposed passive super-twisting second-order sliding mode control strategy. © 2024 Northeast University. All rights reserved.
引用
收藏
页码:1487 / 1497
页数:10
相关论文
共 23 条
  • [1] Wang F, Quan X Q, Ren L T., Review of power quality disturbance detection and identification methods, Proceedings of the CSEE, 41, 12, pp. 4104-4120, (2021)
  • [2] Yi G P, Hu R J., Survey on the power quality question resultant from connection of distributed power generation to the grid, Advances of Power System & Hydroelectric Engineering, 31, 1, pp. 38-46, (2015)
  • [3] Khadkikar V., Enhancing electric power quality using UPQC: A comprehensive overview, IEEE Transactions on Power Electronics, 27, 5, pp. 2284-2297, (2012)
  • [4] Xu X G, Li L F, Wu G B, Et al., Research and challenges of UPQC in power system, Guangdong Electric Power, 30, 4, pp. 1-9, (2017)
  • [5] Tang J S., Design and research of modular multilevel converter(MMC) universal platform, pp. 19-20, (2018)
  • [6] Li P, Yang Y H., Realization for coordinated control of UPQC series unit and shunt unit based on H<sub>∞</sub> control theory, Proceedings of the CSEE, 26, 20, pp. 91-97, (2006)
  • [7] Zhu H, Wang J H, Zheng C C, Et al., Passivity based control of five-level MMC-UPQC, Transactions of China Electrotechnical Society, 32, pp. 172-178, (2017)
  • [8] Liu H M, Jiang C, Cheng Q M, Et al., Research on MMC-UPQC power quality comprehensive management based on passive control in unbalanced power grid, High Voltage Engineering, 47, 4, pp. 1344-1353, (2021)
  • [9] Jiang C, Cheng Q M, Ma X Q, Et al., Differential flat control for unified power quality controller based on modular multilevel converter under unbalanced grid voltage, Transactions of China Electrotechnical Society, 36, 16, pp. 3410-3421, (2021)
  • [10] Sebaaly F, Vahedi H, Kanaan H Y, Et al., Sliding mode fixed frequency current controller design for grid-connected NPC inverter, IEEE Journal of Emerging and Selected Topics in Power Electronics, 4, 4, pp. 1397-1405, (2016)