RESEARCH ON CURRENT SOURCE PV GRID-CONNECTED INVERTER WITH NON-OVERLAPPING TIME AND TRANSFORMERLESS

被引:0
|
作者
Dai Y. [1 ,2 ]
Tang H. [1 ]
Qi Y. [1 ]
Yang X. [1 ]
Chen M. [1 ]
机构
[1] Intelligent Manufacturing Institute, Yibin Vocational and Technical College, Yibin
[2] School of Aeronautics and Astronautics, University of Electronic Science and Technology of China, Chengdu
来源
关键词
grid connected; inverter; leakage current; non-overlapping time; photovoltaic generation;
D O I
10.19912/j.0254-0096.tynxb.2022-0510
中图分类号
学科分类号
摘要
Current source grid- connected inverter (CSGCI) is well known as its no shoot- through problem and superior boost characteristics. However, existing CSGCI not only needs to set the overlap time, but also has the problem of high frequency common mode leakage current. To overcome these imperfections,a new transformerless CSGCI with non- overlapping time (TCSGCI- NT)topology and its unipolar SPWM strategy are proposed. Then,the operating modes and common-mode leakage current of the TCSGCI-NT are analyzed. The commutating current during mode conversion is explored in detail. The analysis result shows that the TCSGCI-NT has the advantages of the non-overlapping time and can completely meet the condition of eliminating common-mode leakage current. Finally,the experimental results verify the correctness of the TCSGCI-NT circuit design and theoretical analysis. © 2023 Science Press. All rights reserved.
引用
收藏
页码:232 / 237
页数:5
相关论文
共 18 条
  • [1] TANG S X, SONG S Y,, YAO F., A transformerless current source photovoltaic grid- connected inverter for leakage current suppression[J], Electrical measurement & instrumentation, 58, 1, pp. 54-61, (2021)
  • [2] GUO X Q, YANG Y, WANG B C., Leakage current reduction of three-phase Z-source three-level four-leg inverter for transformerless PV system[J], Acta energiae solaris sinica, 41, 2, pp. 325-332, (2020)
  • [3] CHEN Y W, JIANG J H, Et al., Review of single-phase current mode PWM inverting technologies[J], Journal of power supply, 15, 1, pp. 111-118, (2017)
  • [4] YANG Z L, WANG Y B,, Et al., An MPC-based ESS control method for PV power smoothing applications [J], IEEE transactions on power electronics, 33, 3, pp. 2136-2144, (2018)
  • [5] YAO Z L., Review of dual- buck- type single- phase grid-connected inverters[J], IEEE journal of emerging and selected topics in power electronics, 9, 4, pp. 4533-4545, (2021)
  • [6] NOGUCHI T., Overlap- time compensation technique for current- source power inverter [J], IET power electronics, 13, 4, pp. 854-862, (2020)
  • [7] WANG Y H,, YE W, SONG R H, Et al., Design of additional active damping for three- phase LCL grid connected inverter based on impedance analysis method [J], High voltage engineering, 47, 8, pp. 2645-2656, (2021)
  • [8] ROY J, XIA Y L,, AYYANAR R., High step- up transformerless inverter for AC module applications with active power decoupling[J], IEEE transactions on industrial electronics, 66, 5, pp. 3891-3901, (2019)
  • [9] KONSTANTINOU G,, Et al., A multi-mode flexible power point tracking algorithm for photovoltaic power plants[J], IEEE transactions on power electronics, 34, 6, pp. 5038-5042, (2019)
  • [10] GUO L L,, ZHANG X, YANG S Y,, Et al., A model predictive control-based common-mode voltage suppression strategy for voltage-source inverter[J], IEEE transactions on industrial electronics, 63, 10, pp. 6115-6125, (2016)