On-line generation method of active power coordinated control strategy for multiple transmission sections in regional power grid

被引:0
|
作者
Liu Y. [1 ]
Xia T. [1 ]
Wang Y. [1 ]
机构
[1] Central Branch of State Grid Corporation of China, Wuhan
关键词
Active power coordinated control; Active power security correction; Linear programming; Multiple transmission sections; Nonlinear programming; Real-time dispatching; Section active power sensitivity;
D O I
10.16081/j.epae.202007008
中图分类号
学科分类号
摘要
A nonlinear programming model based on the section active power sensitivity of DC power flow method is built to solve the active power coordinated strategy of multiple sections, which takes the power of multiple sections within the limit as its control objective and the minimum adjustment quantity as its optimal objective. In order to improve the reliability and speed of model-solving, the auxiliary variables are introduced to transfer the model into a linear programming model. The AC power flow method is used for security check to verify the validity of the strategy. The closed-loop on-line rolling calculation flowchart is designed from three aspects of calculation startup, modeling and solving, and security check. The rolling modification method of node admittance matrix and its inverse matrix suitable for various grid topology change conditions is proposed. The modification strategy of active power adjustment limit of adjustable elements is used to eliminate invalid adjustment measures. The case results verify the effectiveness of the proposed method. The calculation time of each round is within 2 min, which shows that the calculation speed of the proposed method satisfies the requirement of real-time dispatching. © 2020, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:204 / 210
页数:6
相关论文
共 19 条
  • [1] REN Jianwen, WEI Junjiao, GU Yufeng, Preventive control based on multi-objective particle swarm optimization algorithm for cascading trips, Electric Power Automation Equipment, 36, 7, pp. 53-59, (2016)
  • [2] OUYANG J X, LI M Y, ZHANG Z, Et al., Multi-timescale active and reactive power-coordinated control of large-scale wind integrated power system for severe wind speed fluc-tuation, IEEE Access, 7, pp. 51201-51210, (2019)
  • [3] ZHENG Yanhai, ZHANG Xiaobai, QIAN Yumei, Et al., Hybrid algorithm for real-time security constrained dispatch of power system, Automation of Electric Power Systems, 29, 12, pp. 49-52, (2005)
  • [4] CHENG Linyan, HAO Zhiguo, ZHANG Baohui, Et al., Fast eli-mination of overload in transmission line section based on simplified primal-dual interior point method, Automation of Electric Power Systems, 35, 17, pp. 51-55, (2011)
  • [5] XU Yan, ZHI Jing, FAN Shitong, Line overload emergency con-trol based on power sensitivity and minimized economic compensation, Electric Power Automation Equipment, 37, 1, pp. 118-123, (2017)
  • [6] DENG Youman, LI Hui, ZHANG Boming, Et al., Adjustment of equal and opposite quantities in pairs for strategy of active power security correction of power systems, Automation of Electric Power Systems, 23, 18, pp. 5-8, (1999)
  • [7] DENG Youman, ZHANG Boming, XIANG Niande, Et al., Security corrective strategy for the alleviation of active power violations on tie-line-clusters, Automation of Electric Power Systems, 18, 6, pp. 47-51, (1994)
  • [8] YAO Feng, ZHANG Baohui, ZHOU Decai, Et al., Active power security protection of transmission section and its fast algorithm, Proceedings of the CSEE, 26, 13, pp. 31-36, (2006)
  • [9] CHENG Linyan, ZHANG Baohui, HAO Zhiguo, Et al., Fast control algorithm based on integrative sensitivity analysis, Elec-tric Power Automation Equipment, 29, 4, pp. 46-49, (2009)
  • [10] XU Yan, ZHI Jing, A zone-divided emergency control strategy for overload lines based on power sensitivity, Transactions of China Electrotechnical Society, 30, 15, pp. 60-72, (2015)