Influence of Neutral Grounding Mode on the Safety Limit of Lightning Arrester Ground Potential Rise in Station 10 kV system

被引:0
|
作者
Lu H. [1 ]
Wang H. [1 ]
Li Z. [2 ]
Tan B. [3 ]
Li W. [2 ]
Li Y. [1 ]
机构
[1] School of Electrical Engineering and Automation, Wuhan University, Wuhan
[2] Power Research Institute, State Grid Shaanxi Electric Power Company Limited, Xi’an
[3] China Electric Power Research Institute, Wuhan
来源
关键词
arrester; backflash; ground potential rise; neutral grounding modes; safety limit; station power system;
D O I
10.13336/j.1003-6520.hve.20221957
中图分类号
学科分类号
摘要
With the increase of grid capacity and the development of new power systems, the neutral grounding mode of the 10 kV station system has changed. The ground potential rise (UGPR) safety limit of the arrester’s tolerance under the neutral ungrounded system may lead to safety accidents of the arrester under other grounding modes. The electromagnetic transient program ATP-draw can be used to build the model of UGPR counterattack arrester under different neutral grounding modes. By checking the energy absorbed by the arrester under the action of UGPR, the influence of neutral grounding mode on the safety limit of the arrester’s tolerance to UGPR is obtained as follows: Under the neutral ungrounded system, the UGPR safety limit of the arrester is 10~23 kV, which decreases with the increase of the line capacitance to the ground. Under the neutral grounding via arc suppression coil system, UGPR oscillates in the series circuit of the arc suppression coil and the line’s capacitance to the ground, resulting in a lower safety limit of the arrester to withstand UGPR. The safety limit is mainly determined by the out-of-resonance degree and damping rate, and the typical value is 8~9.5 kV. Under the neutral grounding via resistance system, most of the UGPR is coupled to the high voltage bus, so that the safety limit of the arrester to withstand UGPR is higher, which decreases with the increase of the line capacitance to the ground and the neutral resistance. The typical value of the high resistance grounding condition is greater than 15 kV, and the typical value of the low resistance grounding condition is greater than 25 kV. © 2024 Science Press. All rights reserved.
引用
收藏
页码:1499 / 1507
页数:8
相关论文
共 22 条
  • [1] ZOU Jiayong, YU Bo, BAO Weihan, Et al., Influence of the DC component of short circuit current on grounding grid design of UHV substation, High Voltage Engineering, 43, 5, pp. 1621-1627, (2017)
  • [2] LI Chengyang, SU Kan, ZHANG Yi, Et al., Backflash simulation research on substation ground potential rise to low voltage arrester, Insulators and Surge Arresters, 4, pp. 178-183, (2020)
  • [3] SHAO Songtao, JI Chunyi, TAO Tao, Et al., Method for determining safety limits of ground potential rise in high resistivity area substations based on ATP-EMTP, Insulators and Surge Arresters, 1, pp. 104-109, (2019)
  • [4] LI Qian, TAN Bo, WEN Bao, Et al., Calculation and evaluation of ground potential rise control of large grounding grid, Power System Technology, 42, 5, pp. 1675-1681, (2018)
  • [5] QIN Feng, CHEN Wei, WANG Xutong, Et al., Transient response characteristics of metal oxide arrester under strong electromagnetic pulse, High Voltage Engineering, 48, 8, pp. 3326-3333, (2022)
  • [6] TAN Bo, YANG Jianjun, LU Hailiang, Et al., Backflash simulation analysis of ground potential rise on 10 kV arrester, High Voltage Engineering, 39, 5, pp. 1265-1272, (2013)
  • [7] JIA Lili, WANG Ping, LV Fangcheng, Calculation of safety limit value of grounding potential rise in intelligent substation based on EMTP simulation, Insulators and Surge Arresters, 2, pp. 52-58, (2019)
  • [8] LIU Yugen, WANG Jiannan, MI Hongwei, Et al., Optimization research on neutral grounding mode of 10 kV distribution networks, High Voltage Engineering, 41, 10, pp. 3355-3362, (2015)
  • [9] WU Yushuo, YANG Zhihua, HE Dejun, Et al., Single-phase earth capacitance for unearthed neutral systems Engineering calculation method for current, Electrical Technology, 9, pp. 108-111, (2014)
  • [10] YANG Lei, WANG Fochi, ZHAO Tao, Et al., Neutral grounding mode selection and power transmission technology for 10 kV distribution network, Insulators and Surge Arresters, 1, pp. 68-77, (2021)