Research on impact on sub-synchronous resonance risk from DFIG number and grid structure in Guyuan area

被引:0
|
作者
Yin M. [1 ]
Liu H. [2 ,3 ]
Li Y. [2 ,3 ]
Song W. [1 ]
机构
[1] Department of Electrical and Electronic Engineering, North China Electric Power University, Baoding
[2] State Grid Jibei Electric Power Research Institute, North China Electric Power Research Institute Co. Ltd., Beijing
[3] Grid-connected Operation Technology for Wind-Solar-Storage Hybrid System State Grid Corporation Key Laboratory, Beijing
来源
关键词
DFIG; DFIGs and series-compensated power system; Impedance; SSR;
D O I
10.19912/j.0254-0096.tynxb.2018-0747
中图分类号
学科分类号
摘要
In this paper, the equivalent model of wind farms and series-compensated power system in Guyuan is built in RT-LAB. Based on that model, the SSR characteristics of wind farms in Guyuan area under different DFIG numbers and line parameters are investigated through impedance method. The contributions to be included in the paper are as following: 1) The relationship between SSR characteristics and DFIG number is nonlinear in Guyuan area. Under the condition of a given wind speed, there is certain number of DFIGs which will induce worst damping effect. 2) A higher compensation degree results in a less stable system. The SSR risk of the system increases with the increasing of DFIG numbers when the grid strength is high. The relationship between SSR risk and DFIG number is nonlinear when the grid strength is low. © 2021, Solar Energy Periodical Office Co., Ltd. All right reserved.
引用
收藏
页码:174 / 179
页数:5
相关论文
共 16 条
  • [1] DONG X L, XIE X R, LIU H, Et al., SSR characteristics of a wind farm connected to series-compensated transmission system under all operation region of DFIG, Power system technology, 38, 9, pp. 2429-2433, (2014)
  • [2] DONG X L, XIE X R, YANG Y, Et al., Impacting factors and stable area analysis of subsynchronous resonance in DFIG based wind farms connected to series-compensated power system, Power system technology, 39, 1, pp. 189-193, (2015)
  • [3] WANG L, XIE X R, JIANG Q R, Et al., Analysis and mitigation of SSR problems in large-scale wind farms with doubly-fed wind turbines, Automation of electric power systems, 38, 22, pp. 26-31, (2014)
  • [4] WANG W S, ZHANG C, HE G Q, Et al., Overview of research on subsynchronous oscillations in large-scale wind farm integrated system, Power system technology, 41, 4, pp. 1050-1060, (2017)
  • [5] FAN L L, MIAO Z X., Mitigating SSR using DFIG-based wind generation, IEEE transactions on sustainable energy, 3, 3, pp. 349-358, (2012)
  • [6] FAN L, ZHU C, MIAO Z, Et al., Modal analysis of a DFIG-based wind farm interfaced with a series compensated network, IEEE transactions on energy conversion, 26, 4, pp. 1010-1020, (2011)
  • [7] FAN L L, KAVASSERI R, MIAO Z X, Et al., Modeling of DFIG-based wind farms for SSR analysis, IEEE transactions on power delivery, 25, 4, pp. 2073-2082, (2010)
  • [8] MIAO Z., Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network, IEEE transctions on energy conversion, 27, 4, pp. 984-991, (2012)
  • [9] FAN L, MIAO Z., Nyquist-stability-criterion based SSR explanation for type-3 wind generators, IEEE transactions on energy conversion, 27, 3, pp. 807-809, (2012)
  • [10] REN W, LARSEN E., A refined frequency scan approach to sub-synchronous control interaction (SSCI) study of wind farms, IEEE transactions on power systems, 31, 5, pp. 3904-3912, (2016)