Distribution network fault location method based on the sudden drop ratio of feeder active load

被引:0
|
作者
Yang C. [1 ]
Ma J. [1 ]
Yang W. [1 ]
Yang F. [1 ]
Yang X. [2 ]
Huang C. [2 ]
机构
[1] Kunming Power Supply Bureau, Yunnan Power Grid Co., Ltd., Kunming
[2] College of Electrical and Information Engineering, Hunan University, Changsha
基金
中国国家自然科学基金;
关键词
Correlation analysis; Distribution network; Fault analysis; Fault location; Load forecasting; Similar days;
D O I
10.19783/j.cnki.pspc.210361
中图分类号
学科分类号
摘要
It is difficult to accurately and quickly locate the fault section and outage range after power failure in a distribution network with low-level automation. To solve this problem, a fault location and diagnosis method based on sudden drop ratio (SDR) of the feeder active load is proposed. After the feeder SDR exceeds a certain threshold, the active power of each distribution transformer on the faulty feeder is predicted using the historical load data in the metering automation system, and the load proportion of each switch is calculated. By comparing the feeder SDR and the power proportion of each switch, the fault trip switch and power failure range are judged. Analysis of the results of an engineering example show that the method can accurately locate the fault trip switch, and has good real-time performance. It provides a new fault diagnosis technique for a distribution network independent of the distribution network automation system. © 2022 Power System Protection and Control Press.
引用
收藏
页码:144 / 151
页数:7
相关论文
共 23 条
  • [1] GE Weichun, ZHANG Shuo, ZHANG Yanjun, A novel method for fault location of distribution network based on μPMU synchronized measurement data, Power System Protection and Control, 48, 4, pp. 39-46, (2020)
  • [2] XIE Liwei, LI Yong, LUO Longfu, Et al., Distribution network fault location method based on distance matrix and branch coefficient, Proceedings of the CSEE, 40, 7, pp. 2180-2191, (2020)
  • [3] LI Bojiang, ZHENG Shujiang, ZHAN Huiyu, Et al., Fault diagnosis integrated platform based on typical characteristics of electrical signal on the low voltage side of distribution network, Journal of Electric Power Science and Technology, 35, 6, pp. 90-98, (2020)
  • [4] CHEN Wanying, CHANG Haiqing, Research and application of fault analysis and judgment based on multi-source data in distribution network, Electric Power Information and Communication Technology, 18, 12, pp. 43-50, (2020)
  • [5] AHMED A S, ATTIA M A, HAMED N M, Et al., Modern optimization algorithms for fault location estimation in power systems, An International Journal of Engineering Science and Technology, 20, 5, pp. 1475-1485, (2017)
  • [6] GASHTEROODKHANI O A, MAJIDI M, ETEZADI-AMOLI M, Et al., A hybrid SVM-TT transform-based method for fault location in hybrid transmission lines with underground cables, Electric Power Systems Research, 170, pp. 205-214, (2019)
  • [7] XIONG Yufen, QIN Feixiang, HUANG Zhipeng, Et al., High fault-tolerant fault segmentation method based on feeder tree dynamic topology, Power System Protection and Control, 48, 14, pp. 159-164, (2020)
  • [8] FU Yang, TIAN Can, LI Zhenkun, Et al., Temporal and spatial forecasting of distributed PV considering spatial capacity saturation, Power System Technology, 41, 12, pp. 3917-3925, (2017)
  • [9] GUO Zhuangzhi, XU Qixing, HONG Junjie, Et al., A new complementary constraint model and algorithm for fault location of distribution network, Proceedings of the CSEE, 36, 14, pp. 3742-3751, (2016)
  • [10] XU Fengqian, LU Huizhen, WU Shuiping, Et al., Fault location method for low-voltage active distribution network considering information distortion, Proceedings the CSU-EPSA, 33, 1, pp. 94-99, (2021)