Distribution Model of Injection Current in Feeder and Its Application in Single Phase to Ground Fault Detection

被引:0
|
作者
Liu B. [1 ,2 ]
Zeng X. [2 ]
Zhang H. [3 ]
Ma H. [1 ]
机构
[1] College of Energy and Electrical Engineering, Hohai University, Nanjing
[2] Hunan Province Key Laboratory of Smart Grids Operation and Control, Changsha University of Science and Technology, Changsha
[3] School of Automation and Electrical Engineering, University of Jinan, Jinan
来源
基金
中国国家自然科学基金;
关键词
Asymmetric distribution parameters; Current injection; Fault line selection; Sharing coefficient; Single-phase ground fault;
D O I
10.13335/j.1000-3673.pst.2020.1621
中图分类号
学科分类号
摘要
Injection method is one of the important methods of distribution network grounding fault protection. However, an actual grounding fault often contains transition resistance, especially in a high resistance grounding fault, the traditional injection current distribution model and fault detection method does not usually work well. In order to solve the problem of single-phase high resistance grounding line protection in asymmetric power grid, a distribution model of zero sequence fundamental current in feeders and a new method for fault line selection in asymmetric power grid are proposed. By decomposing the components of zero sequence current, it is found that in the case of non-metallic grounding fault, the injected current is distributed in each line, and the proportion distributed is equal to the ratio of the zero sequence admittance of the line to the total admittance of the system, which is defined as "sharing coefficient". According to different neutral grounding modes, trajectory distributions of sharing coefficient with the transition resistance were described, and a single-phase grounding fault identification and fault line selection method based on amplitude and phase characteristics of "sharing coefficient" was proposed. Theoretically, this method can eliminate the influence of asymmetry of the three-phase distributed parameters of power grid, and has the advantage of strong resistance tolerance to transition resistance. In practical application, only the injected current needs to be adjusted and the change of zero sequence current of the detected line to be measured, an easy and simple operation. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:2731 / 2740
页数:9
相关论文
共 22 条
  • [1] pp. 26-37, (2000)
  • [2] ZENG Xiangjun, YU Kun, WANG Yuanyuan, Et al., A novel single phase grounding fault protection scheme without threshold setting for neutral ineffectively earthed power systems, CSEE Journal of Power and Energy Systems, 2, 3, pp. 73-81, (2016)
  • [3] TANG Jinrui, YIN Xianggen, ZHANG Zhe, Survey of fault location technology for distribution networks, Electric Power Automation Equipment, 33, 5, pp. 7-13, (2013)
  • [4] ZENG Xiangjun, YU Yongyuan, YIN Xianggen, Et al., Novel technique for PETERSEN-Coil tuning based on injecting current, Automation of Electric Power Systems, 24, 9, pp. 38-41, (2000)
  • [5] YE Yuqing, MA Xiao, LIN Xiangning, Et al., Active fault locating method based on SOP for single phase grounding faults in the resonant grounding distribution network, Proceedings of the CSEE, 40, 5, pp. 1453-1464, (2020)
  • [6] PAN Zhencun, ZHANG Huifen, ZHANG Fan, Et al., Analysis and Modification of Signal Injection Based Fault Line Selection Protection, Automation of Electric Power Systems, 31, 4, pp. 71-75, (2007)
  • [7] FAN Shuxian, XU Bingyin, ZHANG Qingzhou, Et al., A new method for line selection in distribution system with arc suppression coil grounding with square wave signal injection, Automation of Electric Power Systems, 36, 4, pp. 91-95, (2012)
  • [8] ZENG Xiangjun, HU Jingying, WANG Yuanyuan, Et al., Suppressing method of three-phase unbalanced overvoltage based on distribution networks flexible grounding control, Proceedings of the CSEE, 34, 4, pp. 678-684, (2014)
  • [9] ZHENG Chenling, ZHU Gelan, Distribution network fault segment location algorithm based on Bayesian estimation in intelligent distributed control mode, Power System Technology, 44, 4, pp. 1561-1567, (2020)
  • [10] ZHANG Jianlei, GAO Zhanjun, WANG Zhiyuan, Et al., Fault location method for active distribution based on finite μPMU, Power System Technology, 44, 7, pp. 2722-2730, (2020)