Converter Transformer Noise Equivalent Evaluation Method in Multi-Harmonic Operating Conditions Based on the Electro-Induced Noise Frequency Response Function

被引:0
|
作者
Shichang W. [1 ]
Lingyu Z. [1 ]
Shuyu W. [1 ]
Jian W. [2 ]
Zhiyuan L. [3 ]
Mingxin G. [4 ]
Lü W. [4 ]
Fan Z. [1 ]
Shengchang J. [1 ]
机构
[1] State Key Laboratory of Electrical Insulation and Power Equipment Xi’an Jiaotong University, Xi’an
[2] State Grid Shaanxi Electric Power Company Xi’an
[3] Ultra-High Voltage Company of State Grid Ningxia Electric Power Company, Yinchuan
[4] Electric Power Research Institute of State Grid Shaanxi Electric Power Company, Xi’an
关键词
Converter transformer; noise characteristics; noise equivalent evaluation method; operating conditions; sound field distribution;
D O I
10.19595/j.cnki.1000-6753.tces.221718
中图分类号
学科分类号
摘要
When the noise assessment of the converter transformer before leaving the factory, the basic data generally adopts the test value of the equipment manufacturer or the previous engineering data, and there is a certain gap between the test conditions and the actual working conditions of the site and the actual working conditions, which is difficult to accurately reflect the actual noise situation of the equipment. The electrical equipment in the converter station is larger in size and close to the distance, and a series of reflections, diffraction and other phenomena will occur when obstacles are encountered in the process of noise propagation, and it is difficult to accurately measure the sound source and achieve accurate evaluation of the sound power level of a single device. In order to accurately evaluate the noise level of a single power device, it is particularly important to propose a more accurate factory test method for converter transformer noise. The injection of harmonic current and voltage is the main factor in the rise of the noise level of the converter transformer operation. By using the relationship between the radiated sound pressure of the converter transformer and the square of the excitation voltage and the square of the current, the equivalent evaluation method of the noise of the converter transformer is proposed, taking the equivalent actual multi-harmonic operating conditions as the goal. The single-frequency superposition test is to evaluate the noise level of the converter transformer under the loaded complex frequency excitation by using the result of the single frequency excitation loading noise test through the superposition theorem. Capacitance reduction test is an alternative loading scheme in the case that the capacity of multi-frequency harmonic power supply cannot meet the direct loading, and add 40lgm (reduction ratio) to the capacity reduction test result to obtain the noise level at full capacity. The single-frequency superposition and capacitance reduction tests of the converter transformer are carried out to obtain the radiated noise under different harmonic operating conditions of the converter transformer, and the effectiveness and accuracy of the proposed method are analyzed and compared to verify the noise frequency characteristics and sound field distribution measured and evaluated. The results show that the noise error obtained by the single-frequency superposition test is within 1.8 dB, and the noise error obtained by the capacitance reduction loading test is within 1.6 dB, which greatly improves the accuracy of the noise evaluation of the converter transformer compared with the previous power frequency loading method. The proposed equivalent evaluation test method provides an effective method for converter transformer manufacturers to grasp the noise performance of product operation, and at the same time provides a strong support for the noise design and treatment of converter station. © 2023 Chinese Machine Press. All rights reserved.
引用
收藏
页码:6525 / 6538
页数:13
相关论文
共 39 条
  • [1] Feng Chunlin, Liu Qinglin, Lu Shiming, Et al., Field test on noise reduction effect of AC filter capacitor installation in converter station, Power Capacitor & Reactive Power Compensation, 39, 5, pp. 1-6, (2018)
  • [2] Pei Chunming, Wu Xiaowen, Hu Sheng, Et al., Audible noise distribution and characteristics of a 750 kV substation, High Voltage Apparatus, 52, 1, pp. 101-105, (2016)
  • [3] Ji Shengchang, Shi Yuhang, Zhang Fan, Et al., Review on vibration and noise of power transformer and its control measures, High Voltage Apparatus, 55, 11, pp. 1-17, (2019)
  • [4] Zhai Guoqing, Zhang Bangjun, Structural noise pollution and controlment of transformer, Environmental Pollution & Control, 24, 1, pp. 36-38, (2002)
  • [5] Zhang Chen, Shi Lei, Zhao Yutong, Et al., Analysis of noise and vibration control of urban power distribution room, Chinese Journal of Environmental Engineering, 10, 2, pp. 971-977, (2016)
  • [6] Wang Hua, Chen Jindong, Huang Qingqing, Et al., Noise pollution and control of 10 kV substations in residential zones, Noise and Vibration Control, 35, 4, pp. 107-111, (2015)
  • [7] Guan Hong, Wang Tingfo, Gao Shumin, Et al., Noise influence and treatment of 10kV and 35kV power distribution station, Noise and Vibration Control, 22, 5, pp. 38-41, (2002)
  • [8] Fan Xiaopeng, Li Li, Liu Jiawen, Analysis and control of structural noise pollution of indoor distribution transformers, Noise and Vibration Control, 34, 6, pp. 135-139, (2014)
  • [9] Wu Xiaowen, Zhou Nianguang, Peng Jiwen, Et al., Noise characteristic and relevant factors analysis of power transformers, Journal of Electric Power Science and Technology, 33, 3, pp. 81-85, (2018)
  • [10] Wu Shuyu, Ji Shengchang, Sun Jiantao, Et al., Vibration monitoring and variation law of converter transformer in operation, High Voltage Engineering, 48, 4, pp. 1561-1570, (2022)