Performance investigation of a hybrid liquid-desiccant air conditioning system in a pharmaceutical warehouse: a case study and refined strategy

被引:0
|
作者
Huang, Li [1 ]
Guan, Bowen [2 ]
Qi, Meiwei [3 ]
Liu, Yanbin [2 ]
Yang, Haobo [2 ]
机构
[1] Beijing Tsinghua Tongheng Planning & Design Inst C, Beijing, Peoples R China
[2] Xi An Jiao Tong Univ, Sch Human Settlements & Civil Engn, Xian, Peoples R China
[3] Beijing Tongheng Energy & Environm Sci Res Inst Co, Beijing, Peoples R China
基金
中国博士后科学基金;
关键词
industrial building; humidity control; liquid desiccant; on-site measurements; energy savings; carbon emission;
D O I
10.3389/fbuil.2024.1468537
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Liquid-desiccant-based air conditioning demonstrates significant potential for energy conservation and emission reduction in industrial building applications, contributing to the advancement of a cleaner industrial future. In this study, the on-site performance of a hybrid liquid-desiccant air conditioning system installed in a pharmaceutical warehouse was assessed. The results revealed that blind use of the liquid desiccant caused considerable heat-cold offset in the system, which badly restricted its energy performance. Under the basic conditions, only 81.8% of the total cooling capacity provided by the system could be obtained through the return air, while the remaining 18.2% was wasted owing to the considerable heat-cold offset. A refined system was then proposed to improve the system energy performance. By avoiding the heat-cold offset, the coefficient of performance could be improved from 2.2-2.4 to 2.9-3.1. Moreover, an electricity savings rate of 20.2% was achieved with the refined system over the duration of the entire cooling season. Hence, this work provides valuable insights into energy conservation and emission reduction in industrial air conditioning systems, supporting the process of industrial decarbonization.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Investigation of a compact hybrid liquid-desiccant air-conditioning system for return air dehumidification
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    BUILDING AND ENVIRONMENT, 2021, 187
  • [2] Experimental study on passive-mixing strategy of a liquid-desiccant air-conditioning system
    Lee, Jae-Hee
    Jeong, Jae-Weon
    APPLIED THERMAL ENGINEERING, 2024, 243
  • [3] Simulation on a liquid-desiccant air conditioning system without pump
    Zhao, Wei
    Zhu, Ruiqi
    Kan, Yisong
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2002, 36 (01): : 30 - 34
  • [4] On-site performance investigation of liquid-desiccant air-conditioning system applied in laboratory rodent room: A comparative study
    Guan, Bowen
    Zhang, Tao
    Liu, Xiaohua
    ENERGY AND BUILDINGS, 2021, 232
  • [5] EVALUATION OF COOLING WATER STORAGE FOR LIQUID-DESICCANT AIR CONDITIONING SYSTEM
    Salimizad, Dania
    McNevin, Chris
    Harrison, Stephen
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2014, VOL 8A, 2015,
  • [6] Hybrid heat-pump-driven liquid-desiccant system: Experimental performance analysis for residential air-conditioning applications
    Lee, Jae-Hee
    Jeong, Jae-Weon
    Applied Thermal Engineering, 2021, 195
  • [7] Hybrid heat-pump-driven liquid-desiccant system: Experimental performance analysis for residential air-conditioning applications
    Lee, Jae-Hee
    Jeong, Jae-Weon
    APPLIED THERMAL ENGINEERING, 2021, 195
  • [8] Performance analysis of a hybrid desiccant air conditioning system
    Jia, Chun-Xia
    Dai, Yan-Jun
    Wu, Jing-Yi
    Zhong, Jin-Hua
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2005, 26 (06): : 921 - 923
  • [9] Empirical analysis of indoor air quality enhancement potential in a liquid-desiccant assisted air conditioning system
    Park, Joon-Young
    Yoon, Dong-Seob
    Li, Shiying
    Park, Junseok
    Bang, Jong-Il
    Sung, Minki
    Jeong, Jae-Weon
    BUILDING AND ENVIRONMENT, 2017, 121 : 11 - 25
  • [10] Optimization of NTUm allocation between dehumidifier and regenerator in liquid-desiccant air-conditioning system
    Guan, Bowen
    Liu, Xiaohua
    Zhang, Tao
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 127 : 250 - 259