Low-Voltage Ride-Through Strategy to Doubly-Fed Induction Generator with Passive Sliding Mode Control to the Rotor-Side Converter

被引:1
|
作者
Xu, Jiayin [1 ]
Feng, Peiru [1 ]
Gong, Junwei [2 ]
Li, Shenghu [2 ]
Jiang, Guifen [1 ]
Yang, Hao [1 ]
机构
[1] State Grid Anhui Elect Power Co Ltd, Econ & Tech Res Inst, Hefei 230009, Peoples R China
[2] Hefei Univ Technol, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
关键词
doubly-fed induction generator (DFIG); low-voltage ride-through (LVRT); passive control; sliding mode control; control strategy; COORDINATED CONTROL; WIND TURBINES; INVERTER; SYSTEM;
D O I
10.3390/en17174439
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The doubly-fed induction generator (DFIG) is vulnerable to overcurrent at the stator winding and overvoltage at the DC link due to voltage drop after the grid fault. The large wind farm may have a capacity of several million MWs, whose tripping yields a notable power imbalance and frequency drop in the power systems, which may be avoided by the low-voltage ride-through (LVRT) strategies implemented with the hardware or software. The latter has the merits of low cost and easy to realize, thus studied in this paper. Considering the grid fault uncertainty and DFIG parameters' correlation, this paper newly introduces the sliding mode structure into the passive control to improve the performance of the inner current control loop of the rotor-side converter (RSC), thus proposing a passive sliding mode control (P-SMC) based RSC control strategy to improve the LVRT capability of the DFIG. The time domain analysis with different fault severities, i.e., voltage drops, at the point of public coupling (PCC) is performed. The simulation results with the P-SMC control or not are obtained and compared to verify the control effect and the robustness of the proposed LVRT strategy. This study is beneficial for maintaining power system security against fast-increasing wind power.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] The Control Strategy of The Rotor-Side PWM Converter Based on Doubly-Fed Induction Generator
    Zhao, Meihua
    Fan, Min
    Wu, Xiaoxin
    AUTOMATIC MANUFACTURING SYSTEMS II, PTS 1 AND 2, 2012, 542-543 : 204 - +
  • [2] Low Voltage Ride-Through Control of Doubly-Fed Induction Generator at Synchronism
    Binh, N. V.
    Hofmann, W.
    2014 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES (ICEM), 2014, : 803 - 809
  • [3] Low voltage ride-through control strategy of doubly fed induction generator
    Zhang, Yang
    Huang, Keyuan
    Huang, Shoudao
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 : 153 - 158
  • [4] Low voltage ride-through of doubly-fed induction generator based on rotor series resistor
    Zhang, Wenjuan
    Ma, Haomiao
    Zhang, Guokai
    Zhang, Feige
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2015, 35 (12): : 28 - 33
  • [5] Low voltage ride-through control of doubly-fed induction generator wind turbines with a series grid-side converter
    Yao, Jun
    Liao, Yong
    Li, Hui
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (06): : 98 - 103
  • [6] Low voltage ride through of doubly-fed induction generator connected to the grid using sliding mode control strategy
    Saad, Naggar H.
    Sattar, Ahmed A.
    Mansour, Abd El-Aziz M.
    RENEWABLE ENERGY, 2015, 80 : 583 - 594
  • [7] A low voltage ride-through of strategy for doubly fed induction generator
    Yu, Lan
    Chen, Guocheng
    Song, Xiaoliang
    Cao, Dapeng
    Wu, Guoxiang
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2010, 25 (09): : 170 - 175
  • [8] Symmetrical Low Voltage Ride-Through of the Brushless Doubly-Fed Induction Generator
    Shao, Shiyi
    Long, Teng
    Abdi, Ehsan
    McMahon, Richard
    Wu, Yunxiang
    IECON 2011: 37TH ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2011,
  • [9] Low-voltage ride-through performance of doubly-fed induction generator based on three-level converter excitation
    Cheng, M. (chengmengzeng@126.com), 1600, Electric Power Automation Equipment Press (32):
  • [10] Flexible power control for rotor-side converter of doubly-fed induction generator under unbalanced voltage condition
    Ma J.
    Liu Q.
    Wu J.
    Sun F.
    Wang Y.
    Shen Y.
    Zhou N.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2019, 39 (02): : 196 - 203