Estimation of the Values of Electrical Shock Currents during Live-Line Work in Multi-Circuit, Multi-Voltage HVAC Transmission Lines

被引:0
|
作者
Dziendziel, Agnieszka [1 ,2 ]
机构
[1] Silesian Tech Univ, Fac Elect Engn, Dept Power Syst & Control, PL-441100 Gliwice, Poland
[2] PSE Innowacje Spzoo, Al Jerozolimskie 132, PL-02305 Warsaw, Poland
关键词
live-line work; live-line maintenance; shock current; touch voltage; overhead line; multi-circuit line; multi-voltage line; geometric asymmetry;
D O I
10.3390/en17174276
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This article covers the analysis of voltages induced on the conductors of a de-energized circuit of a multi-circuit, multi-voltage HVAC transmission line. As a result of the multiplied interactions between the circuits in such lines, the expected electrical shock currents (touch currents) to which a lineman performing live work on such a line may be exposed are determined. A number of supporting structures of three- and four-circuit lines with various degrees of geometric asymmetry are analyzed. Analyses have shown that in multi-circuit lines in which circuits of different voltages are carried on a common structure, despite the outage of one of the circuits, touch voltages and electrical shock currents (touch currents) exceeding the permissible values can be expected on its conductors, endangering the safety of the lineman. The arrangements of s in such lines that provide the smallest values of touch currents are indicated.
引用
收藏
页数:17
相关论文
共 23 条
  • [1] Construction and Modeling of Multi-Circuit Multi-Voltage HVAC Transmission Lines
    Dziendziel, Agnieszka
    Kocot, Henryk
    Kubek, Pawel
    ENERGIES, 2021, 14 (02)
  • [2] Switching of elevated electromagnetic and electrostatic induced currents in multi-circuit, multi-voltage HVAC transmission lines
    Lathouwers, Andre
    van der Born, Dennis
    2024 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATIONS, ICHVE 2024, 2024,
  • [3] Chosen analyses for multi-circuit multi-voltage overhead lines capacitances
    Kocot, Henryk
    Dziendziel, Agnieszka
    PRZEGLAD ELEKTROTECHNICZNY, 2020, 96 (08): : 71 - 74
  • [4] Impedance models of multi-circuit multi-voltage overhead power lines
    Kocot, Henryk
    Dziendziel, Agnieszka
    PRZEGLAD ELEKTROTECHNICZNY, 2019, 95 (12): : 257 - 260
  • [5] Methods to Minimize the Effects of Geometric Asymmetry of Multi-Circuit, Multi-Voltage Overhead Lines on Transmission Network Operation
    Dziendziel, Agnieszka
    Kocot, Henryk
    ENERGIES, 2023, 16 (22)
  • [6] Neutral Reactor Structures for Improved Single Phase Auto Reclosing in Multi-Circuit Multi-Voltage Transmission Lines
    Acosta, Jhair S.
    Tavares, Maria Cristina
    Gole, Aniruddha M.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (01) : 298 - 307
  • [7] Benefits and Challenges Resulting from the Development of Multi-Circuit Multi-Voltage Overhead Lines
    Dziendziel, Agnieszka
    Kocot, Henryk
    PRZEGLAD ELEKTROTECHNICZNY, 2022, 98 (03): : 18 - 20
  • [8] Calculation on electrical unbalance of multi-circuit EHV/UHV transmission lines by transmission matrix
    Shi, C. (shichunhua@gedi.com.cn), 1600, Power System Technology Press (36):
  • [9] Transient analysis of multi-circuit overhead transmission lines with two voltage levels
    Nazarcik, Tomas
    Benesova, Zdenka
    PROCEEDINGS OF THE 9TH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRICAL POWER ENGINEERING (ELEKTROENERGETIKA 2017), 2017, : 596 - 601
  • [10] Discharge of Air Gaps During Ground Potential Live-Line Work on Transmission Lines
    Gao, Jiachen
    Wang, Linong
    Li, Guanlin
    Fang, Yaqi
    Song, Bin
    Xiao, Bin
    Liu, Kai
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 187