Research on synchronous condenser’s influences on receiving-end provincial grid and its control strategy

被引:0
|
作者
Zhao J. [1 ]
Meng X. [1 ]
Zhu X. [1 ]
机构
[1] State Grid Jiangsu Electric Power Co., Ltd. Research Institute, Nanjing
关键词
Commutation failure; Control strategy; Multi-infeed short circuit ratio; Short-circuit current; Synchronous condensers; Voltage stability;
D O I
10.19783/j.cnki.pspc.181418
中图分类号
学科分类号
摘要
After synchronous condenser being put into operation as the match project of UHVDC transmission, it’s reasonable to investigate its influence on the operation of large-scale AC-DC hybrid grids, as well as explore its control strategy. Firstly, this paper researches the reactive power characteristics of condenser and builds its reactive power supporting models for different time scales. Secondly, simulations are carried out with the East China Power Grid, the condenser’s influences on voltage characteristics, short-circuit current and commutation failure characteristics are analyzed. The result reveals that condenser could considerably enhance the voltage supporting capability, improve the power grid strength and decrease the risk of UHVDC commutation failure. The validity of theoretical analysis is also verified by the simulation. Finally, a unified dispatch strategy which adopts small difference coefficients and steady lagging-phase operation is proposed for integrating the condenser into AVC system. By adopting the proposed strategy, condenser’s dynamic reactive power supporting function can be sufficiently utilized. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:25 / 32
页数:7
相关论文
共 24 条
  • [1] Zhu X., Wang W., Wang C., Analysis of interaction between UHVAC and UHVDC for Jiangsu power grid, Jiangsu Electrical Engineering, 35, 2, pp. 39-42, (2016)
  • [2] Liu J., Hu Y., Zhao J., Et al., Prospects to the influences of the ultra high voltage grid on Jiangsu power system, Jiangsu Electrical Engineering, 29, 1, pp. 1-3, (2010)
  • [3] Dai H., Wang Y., Li X., Et al., Reactive power compensation device of HVDC converter station and its characteristic analysis, East China Electric Power, 40, 8, pp. 1355-1361, (2012)
  • [4] Cai H., Zhang W., Qi W., Et al., Study on adaptability of phase modifier access to Jiangsu power grid, Power Capacitor & Reactive Power Compensation, 38, 3, pp. 23-27, (2017)
  • [5] Zhao Y., Hua W., Deng H., Et al., Research on the impact of synchronous condenser on Zhejiang Power Grid, Zhejiang Electric Power, 37, 1, pp. 8-12, (2018)
  • [6] Zhang N., Liu J., Zhou Q., Et al., Analysis on the impact of synchronous condenser on DC inverter operating characteristic, Jiangsu Electrical Engineering, 35, 3, pp. 17-20, (2016)
  • [7] Shi X., Mu W., Han J., Et al., Research on control strategy of large synchronous condensers, Electric Power, 50, 12, pp. 44-50, (2017)
  • [8] Moursi M.E., Sharaf A.M., Ei-Arroudi K., Optimal control schemes for SSSC for dynamic series compensation, Electric Power Systems Research, 78, 4, pp. 646-656, (2008)
  • [9] Zhou X., Zhang Y., Liu S., Et al., Voltage control of static var compensator based on novel adaptive dynamic programming, Power System Protection and Control, 46, 12, pp. 77-84, (2018)
  • [10] Cui T., Shen Y., Zhang B., Et al., Influences of 300 MVar synchronous condensers on the stabilities of Hunan power grid, Hunan Electric Power, 36, 3, pp. 1-5, (2016)