Incipient Fault Location for PV Collection System Based on Active Injection

被引:0
|
作者
Zhu R. [1 ]
Jia K. [1 ]
Shi Z. [1 ]
Bi T. [1 ]
Wang C. [1 ]
机构
[1] State Key Laboratory of Alternate Electrical Power System With Renewable Energy Sources, North China Electric Power University, Changping District, Beijing
来源
基金
国家重点研发计划;
关键词
Active injection; Fault location; Incipient fault; PV DC collection system;
D O I
10.13335/j.1000-3673.pst.2020.0526
中图分类号
学科分类号
摘要
Incipient fault location before the short circuit fault offers great help in reducing the recovery time and avoiding the system impact. The incipient faults, however, have too weak signals to be extracted in the time and frequency domain. It is a great challenge to accurately locate the faults without affecting the power delivery. To solve this problem, an active injection based incipient fault locating method is proposed. The high-impedance characteristics of the incipient faults are revealed. The transient resistance index caused by structure changes with disturbance injection is used to locate the incipient faults. Based on PSCAD simulation, the correctness of the proposed method is verified, and its effects on the system voltage stability and power delivery are analyzed. Additionally, the accuracy of the location under noise is verified. The proposed method has high reliability, and can avoid the long time outage of the PV plants. It has good application value. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:67 / 74
页数:7
相关论文
共 18 条
  • [1] Xi Xinze, Huang Wentao, Tai Nengling, Modeling and digital simulation of DC step-up collection system for large-scale photovoltaic power plants, Journal of Shanghai Jiaotong University, 52, 10, pp. 1178-1188, (2018)
  • [2] Zhu Rui, Jia Ke, Zhao Qijuan, Et al., Fault section identification of flexible DC collection system based on collaborated control-protection method[J], Power System Technology, 43, 8, pp. 2825-2835, (2019)
  • [3] Jia Ke, Zhu Rui, Bi Tianshu, Et al., Active non-unit protection for DC collection system based on single-end transient measurement, Proceedings of the CSEE, 39, 6, pp. 1572-1581, (2019)
  • [4] Mao Jianmei, Wang Li, Yang Shanshui, Research on online diagnosis of multi-conductor cables' faults about aircraft power system, Chinese Journal of Scientific Instrument, 37, 9, pp. 1962-1970, (2016)
  • [5] Zhang Shu, He Zhengyou, Zhao Yunhuan, Et al., A fault location method based on C-type traveling wave for the power cable of the 10kV passenger dedicated line, Power System Protection and Control, 40, 14, pp. 51-57, (2012)
  • [6] Dai Lijun, Research on cable online fault location technology of urban rail power supply system, Urban Mass Transit, 22, 12, pp. 35-38, (2019)
  • [7] Furse C, Chung Y C, Dangol R, Et al., Frequency-domain reflectometry for on-board testing of aging aircraft wiring[J], IEEE Transactions on Electromagnetic Compatibility, 45, 2, pp. 306-315, (2003)
  • [8] Liu Yang, Cao Yundong, Hou Chunguang, The cable two-terminal fault location algorithm based on EMD and WVD, Proceedings of the CSEE, 35, 16, pp. 4086-4093, (2015)
  • [9] Gao Shuguo, Liu Hechen, Fan Hui, Et al., PD location method of power cable based on wavelet transform modulus maxima considering wave characteristics, Power System Technology, 40, 7, pp. 2244-2250, (2016)
  • [10] Cheng Jiangzhou, Tang Yang, Xiong Shuangju, Et al., On-line of cable partial discharge localization method based on cable frequency characteristics and signal pulse width, Science Technology and Engineering, 19, 33, pp. 213-219, (2019)