Transient Stability Analysis of Islanded System with Parallel Grid-forming Converters Based on Equivalent Synchronous Power

被引:0
|
作者
Zou Z. [1 ]
Wu C. [1 ]
Wang Y. [1 ]
Tian J. [2 ]
Zhan C. [2 ]
机构
[1] School of Electrical and Information Engineering, Shanghai Jiao Tong University, Shanghai
[2] NR Electric Co., Ltd., Nanjing
基金
中国国家自然科学基金;
关键词
adaptive droop coefficient; equivalent synchronous power; grid-forming converter; islanded microgrid; phase-plane analysis; transient stability;
D O I
10.7500/AEPS20230518011
中图分类号
学科分类号
摘要
With the increasing application of grid-forming (GFM) converters in the microgrid, the effects of GFM converters on the transient stability of the microgrid have received extensive attentions. Different from the single-machine infinite bus system, the frequency and power angle of the islanded system with parallel GFM converters are coupled with each other, and the transient response characteristics are more complex. In order to accurately analyze the transient response of the islanded system with parallel GFM converters, this paper establishes a three-order transient synchronization model of frequency and power angle difference of two GFM converters based on the power angle coupling equation of motion, and analyzes the characteristics of the influence of the power output difference and droop coefficients of two GFM converters on the transient stability. In order to reveal the coupling mechanism of power output and droop coefficient on transient stability, the equivalent synchronous power of parallel GFM converters is analyzed. An adaptive droop coefficient optimization strategy is also proposed based on the power output of GFM converters, which can adaptively increase the equivalent synchronous power of the parallel system and thus improve the transient stability of the system. Finally, the real-time simulation is used to verify the correctness of the three-order transient model and the effectiveness of the proposed control strategy. © 2024 Automation of Electric Power Systems Press. All rights reserved.
引用
收藏
页码:140 / 150
页数:10
相关论文
共 23 条
  • [1] ZHAN Changjiang, WU Heng, WANG Xiongfei, Et al., An overview of stability studies of grid-forming voltage source converters[J], Proceedings of the CSEE, 43, 6, pp. 2339-2359, (2023)
  • [2] WANG X F,, LISERRE M,, Et al., Grid-forming converters:control approaches,grid-synchronization,and future trends—a review [J], IEEE Open Journal of Industry Applications, 2, pp. 93-109, (2021)
  • [3] JAHNS T M., Comparison of grid following and grid forming control for a high inverter penetration power system, 2018 IEEE Power & Energy Society General Meeting (PESGM), pp. 1-5, (2018)
  • [4] Grid-synchronization stability of converter-based resources—an overview[J], IEEE Open Journal of Industry Applications, 1, pp. 115-134, (2020)
  • [5] CHENG Xuekun, LIU Hui, TIAN Yunfeng, Et al., Review of transient power angle stability of doubly-fed induction generator with virtual synchronous generator technology integration system [J], Power System Technology, 45, 2, pp. 518-525, (2021)
  • [6] BLAABJERG F., Impact of synchronous generator replacement with VSG on power system stability, 2020 IEEE 21st Workshop on Control and Modeling for Power Electronics (COMPEL), pp. 1-7, (2020)
  • [7] LIU T,, ZHAO F Z,, Et al., A review of current-limiting control of grid-forming inverters under symmetrical disturbances[J], IEEE Open Journal of Power Electronics, 3, pp. 955-969, (2022)
  • [8] JIANG Qirong, ZHAO Chongbin, Electromagnetic transient synchronization stability with grid-connected inverters[J], Journal of Tsinghua University (Science and Technology, 61, 5, pp. 415-428, (2021)
  • [9] GE Pingjuan, TU Chunming, XIAO Fan, Et al., Transient stability enhancement of a VSG based on flexible switching of control parameters[J], Proceedings of the CSEE, 42, 6, pp. 2109-2124, (2022)
  • [10] Adaptive virtual resistance for postfault oscillation damping in grid-forming inverters[J], IEEE Transactions on Power Electronics, 37, 4, pp. 3813-3824, (2022)