Optimal configuration of main protection for a variable speed pumped storage power generator based on internal fault simulation

被引:0
|
作者
Yin X. [1 ]
Qiao J. [1 ]
Wang Y. [1 ]
Tan L. [1 ]
Lu Q. [1 ]
Li W. [2 ]
机构
[1] State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan
[2] Pumped-Storage Technological and Economic Research Institute, State Grid Xinyuan Company Ltd., Beijing
基金
中国国家自然科学基金;
关键词
internal short circuit fault; main protection optimization; open welding fault; variable speed pumped storage unit;
D O I
10.19783/j.cnki.pspc.226225
中图分类号
学科分类号
摘要
The large-scale variable-speed pumped storage unit has the characteristics of alternating current excitation and variable-speed constant-frequency power generation. It is of practical significance to study the internal fault simulation to clarify the optimal configuration scheme of its main protection. First, a general mathematical calculation model of a variable-speed pumped storage power generation motor is established based on the branch voltage equation and flux linkage equation. This can realize the transient simulation of the internal short-circuit fault and the open-welding line fault of the stator winding under grid-connected full load condition. The fault characteristics of the two types of faults in the simulation results are consistent with the theoretical analysis, and this verifies the correctness of the mathematical calculation model. Then, all possible short-circuit faults and disconnection faults are analyzed according to the winding law of the stator winding, and the established mathematical model is used to simulate and calculate all faults. Finally, it is found that the protection coverage is the best when the main protection configuration scheme is ‘zero sequence transverse and split phase transverse and complete longitudinal differential current protection’ through quantitative analysis and comparison. © 2022 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:1 / 10
页数:9
相关论文
共 29 条
  • [1] ZHANG Zhan'an, CAI Xingguo, Low-carbon dispatch considering operating characteristics of variable speed pumped storage, Proceedings of the CSEE, 36, pp. 51-60, (2016)
  • [2] JIA Defeng, WANG Mingdong, FU Runwei, Et al., RTDS simulation and improvement of excitation-loss protection for pumped storage units, Power System Protection and Control, 49, 3, pp. 158-164, (2021)
  • [3] JIA Defeng, WANG Mingdong, FU Runwei, Et al., RTDS simulation and improvement of excitation-loss protection for pumped storage units, Power System Protection and Control, 49, 3, pp. 158-164, (2021)
  • [4] CHEN Huang, HUANG Hanchang, LI Zhiyuan, Et al., Analysis on the stability characteristics of isolated network of the pumped storage unit, Electrical Measurement & Instrumentation, 58, 11, pp. 113-120, (2021)
  • [5] LIN Li, LI Beichen, SUN Yong, Et al., Multi-time-scale iterative optimal configuration model of pumped storage capacity based on accommodation of high share new energy, Power System and Clean Energy, 37, 1, pp. 104-111, (2021)
  • [6] YAMASHITA H., Upgrade from the fixed speed to adjustable speed (Okutataragi Pumped storage power plant), CIGRE, (2016)
  • [7] DENG Yuwen, WANG Pengfei, Dynamic analysis of variable-speed pumped storage plants for mitigating effects of excess wind power generation, International Journal of Electrical Power and Energy Systems, 134, pp. 1-17, (2022)
  • [8] BIDGOLI M A, YANG Weijia, AHMADIAN A., DFIM versus synchronous machine for variable speed pumped storage hydropower plants: a comparative evaluation of technical performance, Renewable Energy, 159, pp. 72-86, (2020)
  • [9] LIANG Tingting, WANG Kai, CHEN Jun, Study on relay protection scheme of variable speed pumped-storage unit, Hydropower and Pumped Storage, 6, 5, pp. 62-67, (2020)
  • [10] SALOMON C P, SANTANA W C, LAMBERT-TORRES G., Discrimination of synchronous machines rotor faults in electrical signature analysis based on symmetrical components, IEEE Transactions on Industry Applications, 53, 3, pp. 3146-3155, (2017)