SELF OPTIMIZING COMBUSTION CONTROL OF AN OIL-FIRED POWER-STATION BOILER

被引:0
|
作者
JENKINS, PH [1 ]
WILLIAMS, AH [1 ]
机构
[1] CENT ELECT GENERATING BOARD,DEPT SCI SERV,BRISTOL BS13 8AN,ENGLAND
来源
关键词
DIESEL ELECTRIC POWER PLANTS - Control;
D O I
10.1049/ip-d.1981.0009
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Failure to achieve satisfactory control of combustion conditions in an oil-fired boiler leads to undesirable chimney emissions; insufficient combustion air results in the production of black smoke, whereas white acidic smoke is produced by excessive amounts of combustion air. A control strategy has been developed which automatically optimizes the combustion conditions by adjusting the air/fuel ratio to minimize a performance index calculated from measurements of combustion products. This strategy has been implemented on a 100 Mw power station boiler using a standard commercially manufactured process control computer. The paper outlines the engineering of the system and discusses some of the contractual arrangements adopted. This system has been in operation for over three years and has proved capable of tight control of combustion conditions even during rapid load changes. Undesirable chimney emissions have now been virtually eradicated. The success of this system has led to the decision to install similar controls on the 500 Mw boilers at Pembroke Power Station in England.
引用
收藏
页码:50 / 55
页数:6
相关论文
共 50 条
  • [1] IMPROVEMENTS IN STEAM TEMPERATURE CONTROL ON A MODERN OIL-FIRED POWER-STATION BOILER
    DUNNETT, RM
    WELLS, R
    IEE PROCEEDINGS-D CONTROL THEORY AND APPLICATIONS, 1980, 127 (01): : 7 - 12
  • [2] STARTING METHODS FOR GAS-FIRED AND OIL-FIRED BOILER-TURBINE UNITS 800 MW IN CAPACITY AT UGLEGORSK CENTRAL POWER-STATION
    AVRUTSKII, GD
    DOVERMAN, GI
    OSTROVETSKII, RM
    PLOTKIN, ER
    SHMUKLER, BI
    GOMBOLEVSKII, VI
    GONOBOBLEV, AS
    KRASANTSOV, VN
    MATUSHEVSKII, EV
    NAKHIMOV, VI
    SKOPYLATOV, VM
    TUPIKIN, AA
    THERMAL ENGINEERING, 1981, 28 (09) : 527 - 530
  • [3] FLUE-GAS SIDE CLEANING OF OIL-FIRED BOILERS IN HARBURG POWER-STATION
    SPERLING, E
    COMBUSTION, 1979, 50 (08): : 33 - 39
  • [4] EXPERIMENTAL HOUSE LOAD OPERATION AT TANAGAWA NO-2 OIL-FIRED POWER-STATION
    KITADA, M
    MASUYA, T
    TANAKA, H
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (06): : 2796 - 2803
  • [5] HIGH-TEMPERATURE CORROSION INVESTIGATIONS ON AN OIL-FIRED BOILER AT MARCHWOOD POWER STATION
    HOLLAND, NH
    ODWYER, DF
    ROSBOROU.DF
    WRIGHT, W
    JOURNAL OF THE INSTITUTE OF FUEL, 1968, 41 (328): : 206 - &
  • [6] OIL-FIRED BOILER SIMULATION
    TARASIEWICZ, S
    RADZISZEWSKI, P
    MATHEMATICAL AND COMPUTER MODELLING, 1990, 14 : 1075 - 1078
  • [7] OIL-FIRED BOILER CONTROL EXPERIENCE IN AN INDUSTRIAL PLANT
    PAPAVERGOS, PG
    HEDLEY, AB
    JOURNAL OF THE INSTITUTE OF FUEL, 1978, 51 (409): : 212 - 218
  • [8] DISCUSSION ON HIGH-TEMPERATURE CORROSION INVESTIGATIONS ON AN OIL-FIRED BOILER AT MARCHWOOD POWER STATION
    不详
    JOURNAL OF THE INSTITUTE OF FUEL, 1970, 43 (350): : 97 - &
  • [9] OIL-FIRED BOILER CONTROL EXPERIENCE IN AN INDUSTRIAL PLANT.
    Papavergos, P.G.
    Hedley, A.B.
    1978, 51 (409): : 212 - 218
  • [10] IMPROVEMENTS IN COMBUSTION EFFICIENCY THROUGH THE MATCHING OF AIR AND FUEL ON AN OIL-FIRED BOILER
    ARSCOTT, JA
    CHEW, PE
    MA, CJL
    JOURNAL OF THE INSTITUTE OF ENERGY, 1980, 53 (414): : 3 - 15